The Study on Strength and Stiffness of RC Beams Retrofitted with GFRP Wrapping

DOI : 10.17577/IJERTV3IS090266

Download Full-Text PDF Cite this Publication

Text Only Version

The Study on Strength and Stiffness of RC Beams Retrofitted with GFRP Wrapping

Lokesh. A. Doddamani

PG-STUDENT,

Civil Engineering,

Dr. Ambedkar Institute of Technology, Bangalore

Dr. B. Shivakumara Swamy

Prof. & Head of Civil Engineering,

Dr. Ambedkar Institute of Technology, Bangalore

Dr. S. Vijaya

Prof. of Civil Engineering, Dr. Ambedkar Institute of Technology,

Bangalore

Abstract: This work presents the experimental study on strengthening of RC beam with glass fibre reinforced polymer (GFRP). Total nine RC beam specimens were casted & tested in this work. The beam dimensions considered for this study are 150X200X1300 mm. Fe415 grade steel and M25 grade concrete has been used for the casting beams. In this experimental work, three parameters such as balanced, under reinforced and over reinforced RC beam sections were considered. The under reinforced and over reinforced beams were retrofitted with two layers of U-shaped GFRP wrapping on full length of the beam. The beam specimens were tested under two point loading and the load-deflection behavior was observed up to failure. Also the maximum load, the stress- strain behavior and the complete crack patterns were recorded and presented. Experimental investigation reveals that the balanced and over reinforced RC beams retrofitted with two layers of GFRP exhibit more strength and stiffness than the under reinforced RC beams retrofitted with GFRP.

Keywords: strengthening, glass fibre reinforced polymer (GFRP), wrapping, reinforcement,

  1. INTRODUCTION

    In the earlier it was thought that concrete will be a maintenance free Structure. Later on, this myth has proved wrong. Due to majority of Civil Engineering structures being RCC and on account of its requirement of maintenance, quantum of such rehabilitation/strengthening work has also increased tremendously. Constant maintenance and repairing is needed to enhance the life cycle of those structures which are deteriorated. Retrofitting of reinforced concrete element is traditionally accomplished by externally bonding steel plates to concrete.

    Although this technique has proved to be effective in increasing strength and stiffness of reinforced concrete elements, it has the disadvantages of being susceptible to corrosion and difficult to install. In the last decade, the development of strong epoxy glue has led to a technique which has great potential in the field of upgrading structures. Basically the technique involves gluing steel plates or fibre reinforced polymer (FRP) plates to the surface of the concrete. The plates then act compositely

    with the concrete and help to carry the loads. Also recent development in the field of composite materials, together with their inherent properties, which include high specific tensile strength good fatigue and corrosion resistance and ease of use, make them an attractive alternative to any other retrofitting technique in the field of repair and strengthening of concrete elements.

    FRP can be convenient compared to steel for a number of reasons. These materials have higher ultimate strength and lower density than steel. The installation is easier and temporary support until the adhesive gains its strength is not required due to the low weight. They can be formed on site into complicated shapes and can also be easily cut to length on site. A Fiber Reinforced Polymer (FRP) composite is defined as a polymer (plastic) matrix, either thermoset or thermoplastic, that is reinforced (combined) with a fiber or other reinforcing material with a sufficient aspect ratio(length to thickness) to provide a discernable reinforcing function in one or more directions. FRP composites possess some outstanding properties such as: resistance to corrosion, good fatigue and damping resistance, high strength to weight ratio, and electromagnetic transparency. FRP has found an increasing number of applications in construction either as internal or as external reinforcement for concrete structures. It is well known that FRP possesses a major advantage over conventional steel in

    reinforced concrete structures. Civil structures made of steel reinforced concrete are normally susceptible to environmental attacks that lead to the initiation of an electrochemical process which leads to the corrosion of steel reinforcement.

    Bridge deck deterioration due to direct exposure to environment, deicing chemicals and ever increasing traffic loads is one of the most common deficiencies in a bridge system. The use of FRPs for concrete bridge decks and also girders provides a potential for increased service life, economic, and environmental benefits. Beams are the critical structural members subjected to bending, torsion and shear in all type of structures. Similarly, columns are also used as various important elements subjected to axial load combined with/without bending and are used in all type of structures. Therefore, extensive research works are

    being carried out throughout world on retrofitting of concrete beams and columns with externally bonded FRP composites. Several investigators took up reinforced concrete beams and columns retrofitted with carbon fibre reinforced polymer (CFRP)/ glass fiber reinforced polymer (GFRP) composites in order to study the enhancement of strength and ductility, durability, effect of confinement, preparation of design guidelines and experimental investigations of these members. The object of retrofitting of a beam in earthquake resistant frame is that, it must not deform excessively. A beam is subjected to excessive flexural stresses and shear stresses when either member reaches its over strength capacity associated with the hardened plastic hinges.

    The objective of the FRP wrapping is to improve the flexural strength and stiffness of deficient beams due to various causes. Beams are the main structural elements need to be rehabilitated as and when fracture or fault is noticed. As the FRP wrapping is the one of the rehabilitations method, the faulty beams can be strengthened using FRP. Moataz Badavi and Khaled Soudki (2002) carried out the investigation on different issues with GFRP and CFRP confinement on the flexural behavior of reinforced and plain concrete beams and using GFRP and CFRP in the flexural member as confined materials can minimize the amount of cracks and eventually enhance the performance of the structure.

  2. EXPERIMENTAL PROGRAMME

    1. Material Properties:

      The main material used in casting of beams is concrete and it mainly consists of cement, fine aggregate (sand), coarse aggregate and water. These materials are mixed proportionally with designed water cement ratio gives required strength of concrete. OPC-53 grade (ordinary Portland cement) was used for the investigation. It was tested for its physical properties in accordance with Indian Standard specifications. The fine aggregate used in this investigation was clean river sand, passing through

      4.75 mm sieve with specific gravity of 2.60. The grading zone of fine aggregate confirms to zone II as per Indian Standard specifications. Machine crushed granite broken stone angular in shape was used as coarse aggregate. The maximum size of coarse aggregate was 20 mm with specific gravity of 2.64. Ordinary clean portable water free from suspended particles and chemical substances was used for both mixing and curing of concrete. Concrete mix design is carried out to achieve the strength of 25 N/mm2 the proportion is 1 : 2.26 : 3.91. The water cement ratio

      0.45 is used. Fe415 grade steel was used for all reinforcements.

      Fig 1(a) reinforcementdetails for controlled beams

      Fig 1(b) reinforcement details for under reinforced beam

      Fig 1(c) reinforcement details for over reinforced beams

      Glass Fiber Reinforced Polymer (GFRP): Glass fibers are considerably cheaper than carbon and aramid fibers. Therefore glass fiber composites shown in Fig 2 have become popular in many applications. The moduli of fibers are 70-85 GPa with ultimate elongation 2-5% depending on quality. Glass fibers are sensitive to stresses corrosion at high stress levels and may have problems with relaxation. Glass fibers are sensitive to moisture, but with the correct choice of matrix, the fibers are protected.

      Fig 2 GFRP

      The glass fibre supplied by the manufacturer (Harthy Chemicals (India) Pvt. Ltd.) and their properties are summarized in the table1 below.

      Table 1: Properties of GFRP as per the manufacturer

      Properties of GFRP

      Value

      Density of fibre Weight of fibre Fibre thickness Fibre orientation

      Nominal thickness per layer Tensile strength

      Tensile modulus

      2.6 g/cc 920 g/mm2 4 mm

      ±900

      1.5 mm 3400 N/mm2

      73000 N/mm2

      Unsaturated Isopthalic Polyester Resin: Polyester resins are unsaturated resins formed by the reaction of dibasic organic acids and polyhydric alcohols. Polyester resins are used in sheet moulding compound, bulk moulding compound and the toner of laser printers. Wall panels fabricated from polyester resins reinforced with fiberglass so-called fiberglass reinforced plastic (FRP) are typically used in restaurants, kitchens, restrooms and other areas that require washable low-maintenance walls. Polyester resins are thermosetting and as with other resins, cure exothermically. The use of excessive catalyst can, therefore, cause charring or even ignition during the curing process. Excessive catalyst may also cause the product to fracture or form a rubbery material.

      Table 2 Typical properties of cast Thermosetting Polyesters

      Density, g/cc

      12-13

      Tensile modulus, MPa

      55-130

      Thermal expansion, 106/0C

      45-65

      Water absorption, % in 24hr

      .08-0.15

      Accelerator: The function of the accelerator is to accelerate the reaction (polymerization). In the present investigation accelerator used is cobalt octate 2%. The excessive use of Cobalt octoate causes brittleness and early failure of insulation. Cobalt octoate accelerates the catalytic action of Methyl ethyl ketone Peroxide (MEKP) to polymerize unsaturated polyester resin.

      Table 3 Properties of cobalt octoate

      Physical state

      Liquid

      Metal content

      2%

      Tolerance

      ±0.20%

      Colour

      Violet

      Specific gravity at 300

      0.815

      Solid content

      10%

      Catalyst: In this investigation catalyst used is MEKP (Methyl Ethyl Ketone Peroxide). This catalyst is added to polyester resins and vinyl ester resins. As the catalyst mixes with the resin a chemical reaction occurs creating heat which cures (hardens) the resin. It is recommended that the use of MEKP Catalyst should be accurately measured and poured. For 1Kg of resin 1% or 10ml MEKP catalyst is added.

      Table 4 Properties of MEKP catalyst

      Appearance

      Liquid

      Odour

      Pungent

      Colour

      Colourless

      pH

      4.7

      Vapour pressure

      20hPa

      Density

      1060 kg/m3

      Solubility

      <10g/l partly

      Solvents

      Hexane and chloroform

      The form work used for casting of all the specimens consists of mould prepared by wood. Form work was thoroughly cleaned and all the bolts were tighten properly. Shuttering oil was then applied to the inner face of the form work. The reinforcement cage was then placed in position inside the form work carefully keeping in view a clear cover of 25 mm for the top and bottom bars.

    2. specimen details:

      Experimental investigation was carried out on:

      1. Reinforced concrete beams with balanced section (controlled beams).

      2. Under reinforced, over reinforced concrete beams and balanced RC beams retrofitted with Glass fibre reinforced polymer composite sheets.

        The main objective of the investigation was to study the flexural behavior of control RC beams and retrofitted RC beams. Retrofitting is done with DOUBLE LAYER U-WRAPPING of glass fibre reinforced polymer composite bonded onto the whole length of the beam. Initially three control beams (balanced) and then a total of nine retrofitted RC beams were tested, which consists of three under reinforced and three over reinforced concrete beams and three beams with balanced sections were tested. All the beams of size 150mmx200mmx1300mm were casted and tested under two point load with an effective length 1200mm. The mix proportion of M25 grade concrete is cement: fine aggregate: coarse aggregate, 1:

        2.26 : 3.91 with minimum cement content (320Kg/m3) and the concrete was hand mixed. Beams were cured for 28 days then taken out for testing. The surface of the cured beam is full of dirt and grease, to enhance the perfect bonding of composite on the beams the surface of beams must be washed and degreased before proceeding to the application of the resin. Also the edges of the concrete members are grinded off so as to give a mild arc like finish to prevent stress concentration and hence damaging of fibres. This also helps the fibres to give a perfect finish where fibres are wrapped like a continuous cloth as they come in the form of sheets. After the surface preparation resin was applied to the beams, the composite fabric was then placed on top of resin coating and the resin was squeezed through the roving of the fabric with the roller. Air bubbles entrapped at the resin/concrete or resin/fabric interface were to be eliminated. Then the second layer of the resin was applied as shown in fig 3, and GFRP sheet was then placed on top of resin coating and the resin was squeezed through the roving of the fabric and the above process was repeated. Initially three number of controlled beams were tested up to first crack and strengthened with GFRP double layer U wrapping then again tested up to failure. Retrofitted under reinforced and over reinforced beams are tested later on.

        Fig 3 Applying Resin and GFRP

    3. Test Procedure

    All beams were tested under two point load. Each beam was placed on the loading frame in such way that, the centre of the beam and the centre of the loading frame were adjusted and aligned as a line. The effective span of the beam was 1200mm; the load was distributed uniformly by means of mild steel roller placed on the beam along the effective span of the beam, above the roller mild steel I- section was placed for the distribution of load equally on the rollers. A single hydraulic jack was used to apply load. The load was distributed to the beam through the I-section which resulted in two point loads being applied to the specimen. Two dial gauges were used to measure deflection. Deflection under the load and at the mid-span and were noted and strains were measured using demec gauge.

    Dial gauge readings were taken for every 250 kg and demec gauge reading were taken for every 500 kg increment of the load. The cracks patterns were observed and marked by using marker; the initial crack load and maximum load (ultimate failure) were noted down. After failure the load was released slowly and the beam comes to normal position for some extent. The photographs of each specimen were taken and presented in the fig 5(a) and fig 5(b). Also the complete crack patterns and the failure load were recorded in each test. Stress strain curves are also presented in this experiment.

    Figure 4 Test set up (Loading Frame)

    Fig 5(a) Crack pattern for control beam

    Fig 5(b) Crack pattern for retrofitted beam

  3. RESULTS AND DISCUSSIONS

    The test results of experiments conducted on nine RC beam specimens with and without GFRP wrapping has been presented. In that three beams were balanced RC beam specimens, three were under reinforced concrete beams, and three were over reinforced concrete beams. Under reinforced concrete beams and over reinforced concrete beams were retrofitted using double layer U-shape full wrapping of GFRP composites. And balanced control beams were also retrofitted after the testing till first crack. Mid span deflection and deflection under the load are taken into consideration in this work and the same has been presented. Stress strain curves are also presented in this experiment. The load-deflection curve of the structures is generally drawn up to the cracking load. The final failure gives an indication of the overall strength of structures.

    1. Summary Of The Experimental Results

      Table 5 Increase in strength at First Crack for all beams

      Beam Type

      Load at First Crack

      Average Load at First Crack (KN)

      % increase in strength

      CB1

      29.53

      31.2

      CB2

      31.98

      CB3

      31.98

      WCB1

      46.71

      40.56

      30 %

      WCB2

      36.89

      WCB3

      38.11

      WUB1

      51.6

      46.70

      49.67 %

      WUB2

      34.43

      WUB3

      52.83

      WOB1

      55.28

      60.18

      92.88 %

      WOB2

      65.1

      WOB3

      57.53

      Fig 6 Comparison of Load at First Crack for All Beams

      Load carrying capacity of controlled beams at first crack is 31.2 KN, after retrofitted with GFRP, it shows great improvement in strength. The improvement in strength of retrofitted balanced beam is about 30%, in retrofitted under reinforced beam is about 49.67%, in over reinforced beam is about 92% compared to control beam at the first crack as shown in Table 5. The increase in strength

      of retrofitted under reinforced and over reinforced beam is about 12.5% and 35.42% respectively compared to controlled beam at failure as shown in Table 6.

      Table 6 Increase in strength at Failure for all retrofitted beams

      Beam Type

      Ultimate Load at Failure (KN)

      Average Ultimate Load at Failure (KN)

      % increase in strength

      Mode of failure

      WCB1

      51

      48

      All beams were failed in flexure

      WCB2

      46

      WCB3

      47

      WUB1

      55

      54

      12.5%

      WUB2

      44

      WUB3

      60

      WOB1

      59

      65

      35.42%

      WOB2

      71

      WOB3

      65

      Fig 7 Comparison of Ultimate Load for All Retrofitted Beams

      Nomenclature

      CB- controlled beam

      WCB- wrapped control beams (balanced) WUB- wrapped under reinforced beam WOB- wrapped over reinforced beam

      Based on test results obtained ultimate strength, deflection, stress and strain of the all the beams has been calculated and is compared. From the experimental results, the loads v/s deflection curves are plotted including the bar charts shown in fig 6 and fig 7.

    2. LOAD v/s DEFLECTION

      Load v/s deflection curve means a curve in which the increasing flexural loads are plotted on the ordinate axis and the deflections caused by those loads are plotted on the abscissa axis. Up to the service load, the deformation plays an important role while studying the behavior of structures. The load-deflection of the structures is generally drawn up to the cracking load. The final failure gives an indication of the overall strength of structures.

      Mid span deflection and deflection under the load are taken into consideration in this work and the same has been presented. Central deflection of all the beams was more than deflection under load. First crack for CB was observed at 31.2KN and corresponding deflections were 7.6mm (centre) and 6.1mm (under load).

      The load deflection behavior was plotted for all the beams and presented in fig8, fig9, fig10 and fig11.

      Fig 8 Load v/s deflection curves for CB

      Ultimate load carrying capacity of WCB was 48 KN and maximum deflections were 8.72mm (centre) and 8.25mm (under load).

      Fig 9 Load v/s deflection curves for average WCB

      Ultimate load carrying capacity of average WUB was 54KN. and maximum deflections were 12.44mm (centre) and 11.1mm (under load).

      Fig 10 Load v/s deflection curves for average WUB

      Ultimate load carrying capacity of average WOB was 65KN. And maximum deflections were 10.87mm (centre) and 10.29mm (under load).

      Fig 11 Load v/s deflection curves for average WOB

      Fig 12 A typical failure pattern of retrofitted RC beam

      For all the beams load v/s deflection behavior was linear and deflection at the centre was more than deflection under load. There is a small variation in load deflection curve for WCB shown in fig.9 from 35KN to 40KN and same happened in WOB shown in fig.12 there is a small variation from load 55KN to 60KN.

      • Deflection at the centre is more than deflection under the load for all beams.

      • The maximum deflection was observed in retrofitted under reinforced beam (WUB) 12.44 mm at centre and 11.1 mm under load for the load of 46.70KN.

        Combine plot shows the comparison in load v/s deflection behavior of all the beams.

        Fig 13 comparison of load v/s deflection at centre for all beams

        Fig 14 comparison of load v/s deflection under load for all beams

    3. STRESS AND STRAIN BEHAVIOR

    Strain is measured for all the beams in such a way that two points above the neutral axis (compression side) and two points below the neutral axis (tension side).

    Fig 15 measuring strain with demec gauge

    Fig 16 Stress v/s strain curve for CB

    Fig 17 Stress v/s strain curve for WCB

    Fig 18 Stress v/s strain curve for WUB

    Fig 19Stress v/s strain curve for WOB

    The graphs shown in fig16, fig17, fig18 and fig19 represent the stress strain variation of the specimens tested. The strain calculated by measuring the elongation over standard length on the surface at the centre of the beam. This measurement is taken by demec gauge. The beam will yield under service loads if the tensile stress in the concrete exceeds the bending strength of concrete. After formation of cracks, the steel carries the tensile force needed to support the applied load. The cracked beam can continue to support increasing loads until the ultimate capacity is attained due to compression failure of the concrete. The term stress is often defined in two terms force per unit area or the total internal foce within a single member. The mechanical properties of concrete such as its stress-strain curve, depend on a number of factors like rate of loading (Creep),type of aggregate, strength of concrete, age of concrete, curing conditions etc.

    Strengthening technique proved to be efficient in improving the load carrying and deformation resistant capabilities. Experimental investigations reveals that the balanced RC beams and over reinforced concrete beams retrofitted with GFRP exhibits more strength than the than under reinforced concrete beams retrofitted with GFRP.

  4. CONCLUSION

From the test results obtained from the experimental work, control RC beams and retrofitted RC beams are compared and the following summary and conclusions are obtained.

  1. The load carrying capacity of controlled beam at first crack was 31.2 KN and after retrofitted with two layers of GFRP, the improvement of strength was 30 %.

  2. The improvement in load carrying capacity of strengthened under reinforced beam at first crack was 49.67% compared to controlled beams.

  3. The improvement in load carrying capacity of strengthened over reinforced beam at first crack was 92.88% compared to controlled beams.

  4. The improvement in ultimate load carrying capacity of strengthened under reinforced beam was 12.5% compared to retrofitted balanced beam and almost equal to the ultimate load carrying capacity of controlled beams.

  5. The improvement in ultimate load carrying capacity of strengthened over reinforced beam was 35.42% and 20.6% compared to retrofitted balanced beam and controlled beams respectively.

  6. Instead of demolishing and reconstruction of the structures, it is economical to rehabilitate the structural element using GFRP.

  7. The ultimate load carrying capacity of all the strengthened beams is higher when compared to the control beams.

REFERENCES

[1]. Moataz Badawi and Khaled Soudki (2002), The Effect of FRP Wraps on the Tensile Strength of Plain and Reinforced concrete Beams, 4th Structural Speciality Conference, Canada, June 2002, pp. 1-10.

[2]. Tara sen, Shubhalakshmi B.S. and H.N. Jagannatha Reddy (2011),Shear Strength Study Of RCC Beams Retrofitted using Vinyl Ester Bonded GFRP And Epoxy Bonded GFRP, International Journal Of Advanced Engineering Sciences And Technologies, Vol No. 10, April 2011, pp. 70-75.

[3]. C. Natarajan and P. Arun Kumar (2009),Experimental Investigation Of Torsional Behaviour Of Glass Fibre Wrapped Reinforced Concrete Beam, International Journal Of Earth Sciences And Engineering, Vol. 02, No. 01, February 2009, pp. 63-67.

[4]. T. Manikandan and G. Balaji ponraj (2013), Strengthening Of RC Beam Using GFRP Wraps, International Journal of Engineering Trends and Technology, Volume4, May 2013, pp. 1527-1530.

[5]. Nadeem A Siddiqui(2009) carried Experimental investigation of RC beams strengthened with externally bonded FRP composites, Latin American Journal of Solids and Structures 6(2009) 343 362.

[6]. Bhikshma V, M. Koti Reddy b and K. Sunithaa,(2010) Experimental study on rehabilitation of RC beams using epoxy resins. Asian journal of Civil Engineering (building and housing) vol. 11.

[7]. Khaled A. Soudki, Ted Sherwood, and Sobhy Masoud FRP Repair of Corrosion-Damaged Reinforced Concrete Beams Department of Civil Engineering University of Waterloo, Waterloo, Canada.

[8]. Khalifa, A. and A. Nanni (2002), "Rehabilitation of Rectangular Simply Supported RC Beams with Shear Deficiencies Using CFRP Composites," Construction and Building Materials, Vol. 16.

[9]. Balamuralikrishnan R S, and C. Antony Jeyasehar Flexural Behavior of RC Beams Strengthened with Carbon Fiber Reinforced Polymer (CFRP) Fabrics The Open Civil Engineering Journal, 2009.

[10]. Ravichandran1 R S, K. Suguna and P.N. Raghunath ,(2012) An Experimental and Analytical Study On Composite High Strength Concrete Fibre Reinforced Polymer Beams, International Journal of Engineering ,Volume 1.