Seismic Analysis of Multi Storey RCC Building in Different Seismic Zones Using STAAD Pro

DOI : 10.17577/IJERTV15IS100373
Download Full-Text PDF Cite this Publication

Text Only Version

Seismic Analysis of Multi Storey RCC Building in Different Seismic Zones Using STAAD Pro

Aman Kumar

M.Tech Scholar Dept. of Civil Engineering, B.I.T. Sindri, Dhanbad Jharkhand, India

Dr. Nishikant Kisku

Assistant Professor Dept. of Civil Engineering, B.I.T. Sindri, Dhanbad Jharkhand, India

Balram Kumar Mahto

M.Tech Scholar Dept. of Civil Engineering, B.I.T. Sindri, Dhanbad Jharkhand, India

Abstract – The present study investigates and compare seismic-analysis framework for a ten-storey RCC building with a 24 m Ă— 18 m plan and 30 m height. The proposed frame contains 300 Ă— 450 mm beams, 450 Ă— 450 mm columns and 150 mm slabs, with M30 concrete and Fe500 reinforcement. Zones II, III, IV and V are compared under the adopted IS 1893 (Part 1):2016 basis while maintaining constant geometry, mass and modelling assumptions. The methodology covers equivalent static checks and the intended response spectrum analysis in STAAD.Pro. Under the stated loading assumptions, seismic weight is 36,031.50 kN and calculated equivalent static base shear varies from

‌509.71 kN to 1,834.94 kN. Separate shear-building calculations illustrate displacement and inter-storey movement. The Zone V to Zone II action ratio is 3.60, representing a 260% increase when all other linear parameters remain unchanged.

KeywordsRCC building; seismic zones; STAAD.Pro; equivalent static analysis; response spectrum; storey drift.

  1. INTRODUCTION

    Earthquake excitation generates inertia forces that are transferred through floor diaphragms, beams, columns and foundations. The resulting response depends on the mass and stiffness distributions, damping, support conditions and seismic input. Assessment must therefore consider both global demand and deformation. Base shear indicates total horizontal action, while inter-storey movement describes relative deformation between adjacent levels.

    Earlier studies demonstrate the relevance of controlled seismic comparisons. Gupta and Baig [6] considered a G+21 RCC building using STAAD.Pro and compared designs across seismic zones. Tondon and Needhidasan [7] examined a G+8 building in Zones II and IV under the 2002 code framework. Their model heights and code bases differ from the present project; their numerical results cannot be transferred to this building.

    Armo and Jha [8] describe a G+4 building in Zone II with base shear and drift as response measures. This illustrates a single-zone workflow but does not establish four-zone behaviour for the present configuration. The contribution here is a traceable case study linking the supplied geometry, explicit load assumptions, hand checks and a consistent procedure for subsequent solver evaluation.

    ‌The detailed project tables and elevation show ten storeys of 3 m each. Accordingly, the paper uses ten-storey and a height of 30 m throughout.

    1. Objectives and comparison basis

      ‌The objectives are to document a consistent three- dimensional model; establish seismic weight; compare zone-dependent base shear; evaluate displacement and drift in X and Z; and define the member-force and verification records needed for final design assessment. The geometry, stiffness, mass source, damping, soil spectrum and structural-system assumptions are held constant between zones.

      This project examines the influence of seismic-zone

    2. Status

      e available evidence

      coefficient on one fixed building configuration. Both principal horizontal directions are considered. The comparison is intended to isolate the effect of hazard scaling, rather than simultaneously changing the number of storeys, member sizes or mass source.

      The supplied report includes geometry images and native STAAD.Pro model, analysis log or numerical output. The equivalent static benchmark follows the stated code basis; the displacement uses assumed storey springs.

  2. ‌METHODOLOGY AND MATERIAL CHARACTERISATION‌

  1. Modelling and analysis sequence

    The proposed workflow begins with geometry and connectivity checks, followed by materials, section properties, supports and diaphragms. Gravity loads and the seismic mass source are then defined. Static and spectrum cases are prepared for each zone and horizontal direction. Analysis warnings, mass, periods, participation and reactions must be verified before response comparisons and member design.

    TABLE 1. BUILDING CONFIGURATION

    ‌Fig. 1. Elevation and isometric views

    e ten-storey frame.

    Parameter

    Project value

    Plan dimensions

    24 m Ă— 18 m

    Number of storeys

    10

    Storey / total height

    3 m / 30 m

    X bays

    6 Ă— 4 m

    Z bays

    3 Ă— 6 m

    Column positions

    28 per level

    Beam section

    300 Ă— 450 mm

    Column section

    450 Ă— 450 mm

    Slab thickness

    150 mm

    Materials

    M30 / Fe500

    Supports

    Fixed

    1. Seismic details

    TABLE 2. SEISMIC INPUT ASSUMPTIONS

    Parameter

    Value

    Zones

    II, III, IV, V

    Zone coefficients

    0.10, 0.16, 0.24, 0.36

    Importance factor I

    1.0 assumed

    Reduction factor R

    5.0 conditional

    Soil spectrum

    Medium soil assumed

    Damping

    5%

    Analysis basis

    IS 1893 Part 1:2016

  2. ‌Model details

Use X and Z as horizontal axes and Y as vertical. The X coordinates are 0, 4, 8, 12, 16, 20 and 24 m; Z coordinates

are 0, 6, 12 and 18 m. Eleven nodal levels, including the base, produce 308 baseline nodes. The model contains 280 column segments and 450 beams. Each elevated floor has 24 X beams and 21 Z beams, with a combined length of 222 m.

The preliminary concrete elastic modulus is 500030 = 27,386 MPa [2]. Density is assumed as 25 kN/mÂł and Poissons ratio as 0.20. Gross section properties must be distinguished from the effective flexural stiffness used in seismic analysis. Record the appropriate beam and column modifiers under the adopted code basis, including local member axes and any releases.

The use of R = 5 assumes an eligible special moment- resisting frame; material grades alone do not establish that eligibility. Strength, proportions, joints and ductile detailing require verification [2, 3]. The soil spectrum is an assumption because no geotechnical report was provided.

‌A rigid in-plane diaphragm is proposed at each floor, with floor-load transfer to frame members. A floor load does not itself create diaphragm rigidity. If slabs are represented by plates, use appropriate connectivity and mesh refinement, and avoid counting slab self-weight twice. Fixed bases exclude soil flexibility. Infill stiffness, stairs and foundation interaction are outsid the baseline and require separate review when relevant.

  1. Controlled zone cases

    Prepare zone variants from a verified master model. Preserve mass, stiffness, restraints and analysis settings, changing only Z. Include the required positive and negative horizontal actions, eccentricity variants and orthogonal combinations. Symmetry in plan is not a reason to omit accidental torsion or edge-drift checks.

  2. ‌Gravity loading and seismic ma

    For the given model, floor finish and distributed partitions are each assumed as 1.0 kN/m². Occupied-floor imposed load is 2.0 kN/m², with 25% included in seismic weight. Roof imposed load is excluded from seismic mass. Actual wall layouts, parapets, equipment and stairs must replace the allowances where applicable [1, 4, 5].

    TABLE 3. LEVEL WEIGHT

    Component

    Weight kN

    Slab: 432 Ă— 0.15 Ă— 25

    1,620.00

    Beam downstand: 222 Ă— 0.3 Ă— 0.3 Ă— 25

    499.50

    Columns: 28 × 0.45² × 3 × 25

    425.25

    Finish allowance

    432.00

    Partition allowance

    432.00

    Permanent subtotal

    3,408.75

    Seismic imposed load per occupied floor

    216.00

    Occupied floor total

    3,624.75

    Roof total

    3,408.75

    ‌Beam down stand weight avoids slabbeam duplication in the hand benchmark. Full storey-column weight is assigned to the level above. Small joint overlaps are not corrected. The roof partition allowance is retained only for this schedule and must be replaced by the actual roof take-off. Reconcile the software mass source with its own volume and nodal-allocation conventions.

    W = 9(3624.75) + 3408.75 = 36,031.50 kN.

  3. Equivalent static benchmar

    For the adopted bare-frame idealisation, T = 0.075H· = 0.9614 s. On the applicable medium-soil branch, S/g =

    1.36/T = 1.4146. The design coefficient is A = (Z/2)(I/R) (S/g), and base shear is V = AW [1]. Floor force is Q = VWh²/(Wh²). Storey shear is the sum of forces at and above that level. Verify Q = V before comparing with software.

  4. ‌Dynamic analysis and verificati

Define a consistent mass source and spectrum in STAAD.Pro. Check whether the software expects normalised spectral ordinates or acceleration values so that gravity and reduction factors are applied once. Select enough modes to satisfy the adopted participation requirement. Use the appropriate modal combination, including CQC where closely spaced modes require it. Record raw dynamic base shear and any code-required adjustment separately.

Representative strength families include 1.5(DL + LL), 1.2(DL + LL ± E), 1.5(DL ± E) and 0.9DL ± 1.5E, with E

‌representing the required directional and eccentricity action. Drift and service checks require their specified load levels. Independently combined modal peak floor displacements must not simply be subtracted to obtain drift; combine modal relative movements appropriately.‌

III. R TS AND DISCUSSION

  1. Equivalent static base she

    Table 4 and Fig. 2 are independent calculations using Table 3 and the adopted parameters. The same mass and spectral ordinate produce proportional scaling with the zone coefficient.

    TABLE 4. CALCULATED BASE SHEAR

    Zone

    Z

    V kN

    Ratio

    II

    0.10

    509.71

    1.00

    III

    0.16

    815.53

    1.60

    IV

    0.24

    1223.29

    2.40

    V

    0.36

    1834.94

    3.60

    Fig. 2. Equivalent static base shear for the four zone cases.

    Zone III, IV and V demands are respectively 60%, 140% and 260% above Zone II. The 3.60 ratio for Zone V means 360% of the Zone II value, not a 360% increase. These values describe design action, not damage probability or reinforcement demand.

  2. ‌St ey displacement

    Displacement tables are populated using an independent ten-level shear-building example. Uniform springs kX = 250,000 kN/m and kZ = 180,000 kN/m are assumed; they have not been derived from the proposed frame sections. With static storey shear V, relative movement is = V/k and floor translation is u = from the base. The model excludes joint rotations and torsion.

    TABLE 5. ROOF DISPLACEMENT

    Zone

    X mm

    Z mm

    II

    15.95

    22.15

    III

    25.52

    35.45

    IV

    38.28

    53.17

    V

    57.42

    79.75

    Fig. 3. Static displacement profiles.

    TABLE 6. ZONE V FLOOR TRANSLATION

    Height m

    X mm

    Z mm

    3

    7.34

    10.19

    6

    14.66

    20.36

    9

    21.90

    30.42

    12

    28.97

    40.24

    15

    35.73

    49.63

    18

    42.01

    58.34

    21

    47.58

    66.09

    24

    52.21

    72.52

    27

    55.60

    77.22

    30

    57.42

    79.75

    The greater Z response is imposed by the assumed stiffness ratio, kX/kZ = 1.389. Maximum floor translation occurs at the roof in this static example.

  3. ‌Int storey movement

    Inter storey movement is the difference between adjacent level translations within the same static case. It must be distinguished from absolute floor displacement. For a 3 m storey, the adopted 0.004-height reference gives 12 mm at the specified design action [1].

    TABLE 7. MAXIMUM MOVEMENT

    Zone

    X mm

    Z mm

    II

    2.04

    2.83

    III

    3.26

    4.53

    IV

    4.89

    6.80

    V

    7.34

    10.19

    Fig. 4. Inter storey movement

    ‌The first storey has the largest movement in the constant- stiffness because shear accumulates downward. All values are below 12 mm.

  4. Inter etation and missing solver evidence

    Linear static forces and displacements scale with Z when mass and stiffness are unchanged. Modal periods do not change solely because Z changes. Unexpected period differences between zone variants should first trigger a check of modelling inputs and settings.

    ‌IV. C NCLUSION

    1. The project geometry is consistently defined as a 24 m Ă— 18 m ten-storey RCC frame of 30 m height, with 28 column positions per levl. The baseline consists of 308 nodes and 730 frame members before any additional mesh or secondary framing.

    2. Under the explicit load, the seismic weight is 36,031.50 kN. Equivalent static base shear increases from 509.71 kN in Zone II to 1,834.94 kN in Zone V. The ratio is 3.60, corresponding to a 260% increase.

    3. ‌The shear-building demonstrates displacement and drift reporting and predict the actual frame response. The assumed directional springs determine the relative X and Z responses. Their values can establish member adequacy or a need for shear walls.

ACKNOWLEDGEMENT

‌The author acknowledges the guidance of Dr. Nishikant Kisku and the academic support of the Department of Civil Engineering, B.I.T. Sindri, as recorded in the supplied project manuscript.

Data availability and manuscript status

The source material consists of the authors project manuscript and geometry views. Tables 37 and Figs. 24 contain independent calculations. Native STAAD.Pro input and output files were available.

‌REFERENCES

  1. Bureau of Indian Standards, IS 1893 (Part 1):2016, Criteria for Earthquake Resistant Design of Structures General Provisions and Buildings, New Delhi, 2016.

  2. Bureau of Indian Standards, IS 456:2000, Plain and Reinforced ConcreteCode of Practice, New Delhi, 2000.

  3. Bureau of Indian Standards, IS 13920:2016, Ductile Design and Detailing of Reinforced Concrete Structures Subjected to Seismic ForcesCode of Practice, New Delhi, 2016.

  4. Bureau of Indian Standards, IS 875 (Part 1):1987, Design Loads for Buildings and StructuresDead Loads, New Delhi, 1987.

  5. Bureau of Indian Standards, IS 875 (Part 2):1987, Design Loads for Buildings and StructuresImposed Loads, New Delhi, 1987.

  6. A. K. Gupta and M. A. Baig, Comparison and Analysis of Multistoried R.C.C Building in Different Seismic Zones, International Journal of Advance Research, Ideas and Innovations in Technology, vol. 3, no. 4, paper V3I4-1233, 2017. www.ijariit.com/manuscripts/v3i4/ V3I4-1233.pdf

  7. B. K. Tondon and S. Needhidasan, Seismic Analysis of Multi Storied Building in Different Zones, International Journal of Trend in Scientific Research and Development, vol. 2, no. 2, 2018. www.ijtsrd.com/papers/ijtsrd9490.pdf

  8. P. Armo and B. K. Jha, Seismic Analysis and Design of Multi-Storey Building in STAAD Pro for Zone II, International Journal of Engineering Research & Technology, vol. 11, no. 5, paper IJERTV11IS050362, 2022. www.ijert.org/seismic-analysis-and-design-of-multi- storey-building-in-staad-pro-for-zone-ii