Performance And Optimization Of Capillary Tube Length In A Split Type Air Conditioning System

DOI : 10.17577/IJERTV1IS7050

Download Full-Text PDF Cite this Publication

Text Only Version

Performance And Optimization Of Capillary Tube Length In A Split Type Air Conditioning System

Performance and Optimization of Capillary Tube Length In a Split Type Air Conditioning System

D.V.Raghunatha Reddy1 Dr P.Bhramara2 Dr K.Govindarajulu3

1 Assit.Prof, Dept of ME, A.T.R.I.Uppal, Hyderabad-500039, A.P, India.

1 Research Scholar, Dept of ME Dept., J N T U.A, Anantapur, A. P., India

2Assoc. Prof, Dept. Of ME, JNTUH College of Engineering Hyderabad A.P India

Professors, Dept of ME, JNTUA College of Engineering Ananthapur A.P, India

3

ABSTRACT

The objectives of this research were to evaluate the optimization of a capillary tube in a split- type air conditioning system and to determine the coefficient of performance (COP) of the system. The optimization was determined by mathematical calculation to evaluate COP of a split-type air conditioning system within 5 different sizes of capillary tube. Following this, the experimental equipment was designed and constructed to verify the COP data obtained from the calculation. The results found that from the theoretical analysis and experiment, the COP was changing in a direction contrary to the diameter of the capillary tube. When the capillary tube diameter is smaller, COP values tend to be higher.

KEYWORDS: Air-conditioning system, Optimization of Capillary tube, BAC Lab, Mathematical and Experimental Calculations, COP

I INTRODUCTION

Air conditioning and refrigeration systems play an important role in industry, infrastructure and households. The industrial sector includes the food industry, textiles, chemicals, printing, transport and others. Infrastructure includes banks, restaurants, schools, hotels and recreational facilities. Therefore, installation, repair and maintenance of equipment to function properly are important for the operations associated with those activities. At present reducing pressure valves used in air conditioning and refrigeration systems can be classified into two types: expansion valves and capillary tubes. The capillary tube is made from copper pipe, with a diameter around 0.5 mm to 5 mm and length around 0.5 m to 5 m. Its use depends on power and load capacity of the system. The capillary tube is often used with small cooling load or small changing load systems, such as refrigerators, water coolers and small air conditioners.

Problems from the blockage in the capillary tube results in lower injection of refrigerant into the evaporator, so there will be less cooling. Typically this problem c a n be solved b y changing a new capillary tube. However, this also results in refrigerant being released from the system, which makes for higher cost and time wastage. Furthermore, the size of the replacement capillary tube must be the same and some sizes are difficult to source, which makes the maintenance cost even higher.

Taking into consideration these problems, the objective of this research is to determine the appropriate size of a new capillary tube that can replace the old blocked one and to construct an experimental equipment system with different capillary tubes to measure the real values. The resulting values will show which size of capillary tube can be used instead of the old one. This will be more convenient for maintenance and will save costs when fixing air conditioning and refrigeration systems.

    1. Objective:

      1. To evaluate the performance of an air conditioner system for different capillary lengths, mathematically and experimentally.

      2. To compare experimental and mathematical model and select best capillary length for the system

II Mathematical Solution for Capillary Tube:

Theoretically, the appropriate size of capillary tube can be calculated from the refrigerant effect, Coeficiento f performance (COP) and others. The system is assumed to work as an isentropic process and there are five different sizes of capillary tubes in this calculation.

To undertake simulation with any value it is necessary to use the results from the previous test in t h e r e a l w o r k e n v i r o n m e n t . The c o m p r e s s o r i n f o r m a t i o n , RNB5522EXC, i s f r o m t h e compressor manufacturer and has been adjusted into the theoretical calculation to determine the value of the variables depending on the different size of capillary tubes by evaluating COP at the various states of capillary tubes in the isentropic process. Theoretically, the appropriate size of capillary tube can be decided by evaluating coefficient of performance (COP) of the system for the different capillary lengths. Five different sizes of capillary tubes are considered for analysis.

To undertake simulation with any value it is necessary to use the results from the previous test in the real work environment. The compressor information, RNB5522exc, is from the compressor manufacturer and has been adjusted into the theoretical calculation to determine the value of the variables depending on the different size of capillary tubes by evaluating COP at the various states of capillary tubes in the isentropic process.

    1. MATHEMATICAL CALCULATIONS:

      Mass Flow Rate Equation:

      Substituting the mass flow rate data in the above equation we have: From above equation the constants we will get as:

      C1= 117.7158,

      C2= 2.7149,

      C3= -0.2007,

      C4= -0.8751,

      C5= 8.5×10-3,

      C6= 0,

      C7= 0.0197,

      C8= 3.3866×10-4,

      C9= 3.1417×10-4

      Substituting the constants in the equation (A) the mass flow rate equation can be written as follows:

      m = 117.7158 + 2.714966 – 0.20077 – 0.875139 + 8.5913 10-3 + 0.019749

      + 3.38664 10-4 – 3.14175 10-4

      substituting the various condenser and evaporator temperatures in the above equation well get the mass flow rate (kg/h) as below

      Mass flow rate data of compressor RNB5522EXC

    2. Mass Flow Rate (g/s)At Various Condenser And Evaporatortemperature:

      Condenser Temperature(°C)

      Mass flow rate(g/s)

      Evaporator Temperature (°C)

      0

      5

      10

      40

      26.793

      31.917

      38.243

      45

      26.542

      31.286

      37.475

      50

      26.510

      31.455

      36.438

      55

      26.547

      31.278

      34.735

      60

      26.704

      31.148

      33.553

      Dimensions of five different capillary tubes used for calulations and experiment are D = 1.524mm (0.06). diameter is constant for all the lengths of the tube.

      L1 = 0.889m (35) L2 = 0.8382m (33) L3 = 0.762m (30)

      L4 = 0.635m (25), L5 = 0.508m (20).

    3. Mass flow rate through the capillary tube can be evaluated from the equation below:

      Where

      m = Flow rate R-22 (g/s). D= Diameter ( mm)

      L= Length (m) T=Condenser Temperature.(oC)

      DSC=Degree of Sub cooling (oC) C1= constant = 0.249029

      C2= constant = 2.543633 C3= constant = -0.42753 C4= constant = 0.746108 C5= constant = 0.013922

      Mass flow rate equation can be rearranged to get sub-cooled temperature:

      The above equation is valid for the single capillary system but the equation is modified for twin capillary system as follows:

      Substituting the values of mass flow rate and dimensions of the tube in the abve equation sub-cooled temperatures can be shown follows

    4. Model calculation for degree of sub-cooling(DSC) :

    5. Degree of Sub-Cooling (°C) At Various Condenser And Evaporator Temperatures

Condensor

Temperature (°C)

Evaporator

Temperature (°C)

Degree of sub-cooling (°C)

Tube 1

(L1=35)

Tube 2

(L2=33)

Tube 3

(L3=30)

Tube 4

(L4=25)

Tube 5

(L5=20)

40

5

18.16

17.376

16.105

13.674

10.698

10

23.801

23.016

21.745

19.314

16.338

45

5

14.797

14.012

12.741

10.310

7.334

10

20.427

19.643

18.372

15.940

19.964

50

5

12.513

11.728

10.457

8.025

5.049

10

17.099

16.315

15.044

12.612

9.636

55

5

10.118

9.333

8.062

5.631

2.655

10

13.388

12.603

11.332

8.901

5.925

60

5

7.963

7.179

5.908

3.976

0.5005

10

10.283

9.498

8.227

5.796

2.820

The values of degree of sub-cooling from the above table is used to calculate C.O.Ps by assuming 10°C of superheat at the inlet of the compressor

The C.O.Ps found out through the above mentioned procedure are tabulated as follows

C.O.PS at various condenser and evaporator temperatures

Condensor Temperature (°C)

Evaporator Temperature (°C)

C.O.P

Tube1

(L1=35)

Tube2

(L2=33)

Tube3

(L3=30)

Tube4

(L4=25)

Tube5

(L5=20)

40

5

7.326

7.286

7.220

7.095

6.780

10

9.095

9.047

8.970

8.821

8.639

45

5

6.099

6.063

6.005

5.894

5.758

10

6.633

6.596

6.536

6.421

6.28

50

5

5.164

5.132

5.080

4.980

4.858

10

6.231

6.194

6.134

6.019

5.878

55

5

3.417

3.394

3.358

3.287

3.201

10

4.150

4.123

4.080

3.999

3.897

60

5

3.326

3.302

3.264

3.191

3.101

10

4.042

4.014

3.969

3.882

3.776

III EXPERMIENTAL PROCEDURE:

Experiments are conducted at Tecumseh products India pvt.ltd in the balance ambient calorimeter lab.

    1. BAC test lab

      BAC lab was established to test the room air conditioning appliances (window and split type) as per different standards under balanced temperature conditions. The lab is divided into two test rooms namely indoor test room and outdoor test room. Each test room is enclosed by another chamber isolating the test rooms from the atmospheric influence by creating a space known as controlled air space. A constant dry bulb temperature equal to that of the dry bulb temperature inside the test room is maintained within the controlled air space shows the view of the balance ambient calorimeter (BAC) lab

      BAC lab view

      Each test room consists of the following equipment

      • Chillers: Used to maintain the ambient temperatures.

      • Blowers: Used to distribute the air inside the test room in order to maintain equilibrium.

      • Steamers: Used to maintain the relative humidity.

      • Heaters : Used to maintain the dry bulb temperature

      • Temperature sensors: Used to measure temperature inside the room

      • Energy meter: Used to calculate power consumption of appliance and lab equipment.

      • Temperature controllers : Used to maintain dry bulb and wet bulb temperatures

      • Computer: The lab is pre-programmed, controlled and monitored by software called as Lab view. The software automates the lab avoiding manual intervention reducing error levels.

        1

        8

        2

        7

        5

        3

        4

        6

        dry bulb temperature / outdoor wet bulb temperature

        Monitored outdoor dry bulb temperature / outdoor wet bulb temperature

        Monitored indoor dry bulb temperature / indoor wet bulb temperature

        Indoor and outdoor controlled air space dry bulb temperature

      • Total OD cooling capacity indicator

      • Stabilization indicator

      • Outdoor and indoor unit test rooms dry bulb and wet bulb temperatures

      • Once the standard is defined in the program the temperatures defined in the standard are maintained inside the test rooms with the aid of steamers, blowers, heaters and chillers through an automated process.

      • The unit starts running the varying dry bulb and wet bulb temperatures can be monitored on the calorimetric screen

      • The dry bulb and wet bulb temperatures are stabilized over the defined values the in-condition light turns and a report is generated.

      • The report generated narrates the complete test summary. Therefore the judgment can be made basing in the cooling capacity and EER obtained from the report.

3.1Results from Experiment:

Measurement position

Symbol

Unit

Capillary tube

Tube 1 (L1=35)

Tube 2 (L2=33)

Tube3 (L2=30)

Tube 4 (L2=25)

Tube 5 (L2=20)

Compressor

pressure

P1

P2

Bars

Bars

4.481

22.0632

4.495

21.787

4.757

20.546

4.964

20.063

5.067

19.987

Compressor temperature

T1 T2

14.78

87.1

14.96

86.7

15.23

85.9

15.39

86.2

15.5

86.6

Condenser temperature

T3

53.46

3.67

54.29

55.08

55.28

Evaporator temperature

T4

8.2

9.5

9.9

10.2

10.5

C.O.PS

C.O.PS

2.318

2.254

2.178

2.151

2.096

IV RESULTS AND DISCUSSIONS:

The performance of 1.5tonn split type air conditioning system is evaluated mathematically and experimentally. The results from mathematical model and experiments are discussed in the following sections: Mathematical model:

Mathematically C.O.PS are evaluated at various condenser and evaporator temperatures by considering the sub- cooled temperature and assuming the 5°C of superheat at the inlet of compressor.

    1. The Results Are Tabulated in Table C.O.PS evaluated at Various Evaporator and Condenser Temperatures:

      Condensor

      Temperature (°C)

      Evaporator

      Temperature (°C)

      C.O.P

      Tube1

      (L1=35)

      Tube2

      (L2=33)

      Tube3

      (L3=30)

      Tube4

      (L4=25)

      Tube5

      (L5=20)

      40

      5

      7.326

      7.286

      7.220

      7.095

      6.780

      10

      9.095

      9.047

      8.970

      8.821

      8.639

      45

      5

      6.099

      6.063

      6.005

      5.894

      5.758

      10

      6.633

      6.596

      6.536

      6.421

      6.28

      50

      5

      5.164

      5.132

      5.080

      4.980

      4.858

      10

      6.231

      6.194

      6.134

      6.019

      5.878

      55

      5

      3.417

      3.394

      3.358

      3.287

      3.201

      10

      4.150

      4.123

      4.080

      3.999

      3.897

      60

      5

      3.326

      3.302

      3.264

      3.191

      3.101

      10

      4.042

      4.014

      3.969

      3.882

      3.776

    2. Mathematical results by changing Condenser temperature and Evaporator temperature:

      Capillary tubes

      Mathematical results

      Condenser

      Temperature (0c)

      Evaporator

      Temperature (0c)

      COP

      Tube 1

      53.46

      8.2

      6.212

      Tube 2

      53.67

      8.9

      6.296

      Tube 3

      54.29

      9.3

      6.274

      Tube 4

      55.08

      9.5

      6.197

      Tube 5

      55.28

      9.9

      6.234

      Length Of The Capillary Vs C.O.P (Mathematical Model):

      6.32

      6.3

      6.28

      6.26

      6.24

      6.22

      6.2

      6.18

      6.16

      6.14

      889 838 762 635 508

      cop

    3. Comparison between the Mathematical Results And Experimental Results

From the mathematical and experimental models it is found that Tube 2(largest length) has the maximum C.O.PS

    1. and 2.254 respectively. The experimental results correspond with the results from calculation (mathematical model) or at least they show the same trend. From the above graphs it is apparent that when the capillary tube length is increased C.O.P is higher.

      Length of the Capillary Vs C.O.P (From Experiments)

      2.28

      2.26

      2.24

      2.22

      2.2

      2.18

      2.16

      2.14

      2.12

      2.1

      2.08

      889 838 762 635 508

      cop

      Capillary tube length in mm

      Comparison between Experimental and Mathematical Results

      5

      4.5

      4

      3.5

      3

      2.5

      2

      1.5

      1

      0.5

      0

      Category 1

      Category 2

      Category 3

      Category 4

      Series 1

      Series 2

      Graph shows the comparison between experimental and mathematical values. Around 30-35% of deviation was noticed between mathematical and experimental values. This deviation in the mathematical and experimental values might be due to the following reasons:

      • Frictional losses in the compressor were not considered in analysis.

      • Electrical losses are also not considered.

      • Fan motor efficiency is also not considered

V Relative COP:

The ratio of the actual COP to theoretical COP is known as Relative COP

36

35.5

35

34.5

34

33.5

889 838 762 635 508

Relativ

  1. NOMENCLATURE:

    A cross-sectional area (m2)

    D diameter (m)

    H specific enthalpy (kJ/ kg-1)

    1. Boltzmanns constant

    2. length (m)

    3. mass flow rate (kg /s)

    P pressure (kPa)

    s entropy (kJ/ kg K)

    T temperature ()

    V velocity (m/s)

    v specific volume (m3/ kg)

    x vapor quality (dimensionless)

    Cp specific heat (kJ/ kg K)

    Dc capillary tube diameter (m)

    Ds suction line diameter (m)

    1. gravitational acceleration (m/ s2)

    2. specific enthalpy (J/ kg)

    Q heat transfer rate (W)

    s specific entropy (J/kg K)

    1. temperature (K)

    2. overall heat transfer coefficient (W/m2 K)

    3. velocity (m/ s)

    Hc heat transfer coefficient in capillary tube (W/m2 K)

    Hs heat transfer coefficient in suction line (W/m2 K)

    Lf final length of capillary tube (m)

    Lhx heat exchange region length (m)

    Lin initial length of capillary tube (m)

    Lsp single-phase flow length (m)

    Ltp two-phase flow length (m)

    m mass flow rate (kg/sec)

    z position (m)

  2. CONCLUSIONS:

    From the experimental work, the following conclusions are drawn for a capacity of 1.5 Tons Split type Air- Conditioning system, at Tecumseh at Hyderabad.

    All the parameters are at standard test conditions as per IS 10617 for R-22 Refrigerant. Condenser Temperature: 50-55°C

    Evaporator Temperature: 7- 10°C INDOOR UNIT CONTIONS:

    Dry Bulb Temperature (DBT) – 27°C Wet Bulb Temperature (WBT) – 19°C OUTDOOR UNIT CONTIONS:

    Dry Bulb Temperature (DBT) – 35°C Wet Bulb Temperature (WBT) – 24°C Capillary Tube size: 0.06"×33"×2 nos.

    1. When the diameter is held constant and lengths of the capillary tube is varied, the length 33"(838 mm) gives the maximum COP of the system.

    2. When the length of capillary tube decreases, as the refrigeration effect also decreases. When the capillary tube diameter is kept constant.

    3. The Degree of sub cooling increases as the length of the tube increases. Practically, maximum degree of sub-cooling that can be achieved is 15°C. Because, compressor work will also increases as the degree of sub cooling increases.

    4. Compressor work will be minimum in between the range of evaporator temperature 8 -10 °C for using Air-Conditioning system

    5. Normally the Actual COP to theoretical COP (i.e. Relative COP) is 32-35%. For Split type Air- Conditioning system.

Comparison between the standard size and recommended capillary tube size:

S.NO

Capillary tube size

COP

Relative COP

1

0.06"×27"×2 nos

2.1645

34.9993

2

0.06"×33"×2 nos

2.254

35.801

REFERENCES:

  1. Akkarat Poolkrajang and Nopporn Preamjai Optimization of capillary tube in air conditioning system, Asian Journal on Energy and Environment.

  2. C.P Arora, Refrigeration and Air conditioning. Tata McGraw-Hill Book Company.

  3. Balance Ambient Test Facility Lab manual (BATAF) Tecumseh Products India Pvt. Ltd.

    1. Stocker, W.F. and Jones J.W. (1982), Refrigeration & Air Conditioning. McGraw- Hill Book Company, Singapore.

    2. Jung, D., Park, C. and Park B. (1999). Capillary tube selection for HCFC22 Alternatives, Department of Mechanical Engineering, Inha University, Inchon, Korea

    1. ASHRAE (2001). 2001 Ashrae Handbook Fundamentals SI Edition. Atlanta, USA.

    2. A Text book of Refrigeration and Air conditioning by R.S.Khurmi and J.K.Gupta.

Authors

D.V.Raghunatha Reddy B.Tech. (ME) from JNT University College of Engineering, Hyderabad M.Tech.(R&A.C) from JNTUAnantapur, working as a Assistant Professor i n M E Dept, A u r o r a s T e c h n o l o g i c a l R e s e a r c h a n d I n s t i t u t e U p p a l , Hyderabad, and pursuing Ph.D from JNTUniversity, Anantapur His current research interests are in the areas of simulation of refrigeration systems in different techniques.

P.Bhramara, B.Tech. (ME) from JNT University College of Engineering, Hyderabad M.Tech.(R&A.C) from Coimbatore Engineering College Coimbatore, and completed Ph.D.(Heat Transfer) from JNTU, Hyderabad in . She has one year of Industrial experience and 12 years of teaching experience. Presently she is working as Associate Professor, JNTU College of Engineering, JNTUH, Kukatpally, Hyderabad. Her research interests in Two Phase Heat Transfer, Instrumentation & Data acquisition Refrigeration & Air Conditioning, Computational Fluid Dynamics.

K.Govindarajulu B. Tech. (Mechanical) S.V.U. Tirupati, M. Tech. (Heat Power) JNTU, Hyderabad and Ph.D. (Boiling Heat Transfer), I.I.T., Rookee, Professor in Mechanical Engineering from JNTU Ananthapur He has 30 years of teaching experience. He has many research publications in various international and national journals and conferences, and he has received as a BEST TEACHER AWARD IN THE YEAR 2012

Leave a Reply