Design of an Air Distribution System for a Multi- Story Office Building

DOI : 10.17577/IJERTCONV3IS20109

Download Full-Text PDF Cite this Publication

Text Only Version

Design of an Air Distribution System for a Multi- Story Office Building

Chuneshwar Lal Verma

Asst. Prof. Mechanical Engineering Department Rungta Engineering College, Raipur

Raipur, C. G., India.

Puneshwar Verma

Asst. Prof. Mechanical Engineering Department Parthivi College of Engineering and Mgmt., BHILAI-3 Durg, C. G., India.

Swapnil Shukla

Asst. Prof. Mechanical Engineering Department Parthivi College of Engineering and Management, BHILAI-3

Durg, C. G., India.

Abstract Earlier the use of air conditioning for comfort purpose was considered to be expensive, but now-a-day, it has been a necessity for all human beings. Window air conditioners, split air conditioners are used in small buildings, offices etc. But, when the cooling load required is very high such as big buildings, multiplex, multi-story buildings, hospitals etc. centralized unit (central air conditioners) used. The central ACs systems are installed away from building called central plant where water or air is to be cooled. This cooled air not directly supplied to the building rooms. When the cooled air cannot be supplied directly from the air conditioning equipment to the space to be cooled, then the ducts are provided. The duct systems carry the cooled air from the air conditioning equipment for the proper distribution to rooms and also carry the return air from the room back to the air conditioning equipment for recirculation. When ducts are not properly designed, then it will lead to problem such as frictional loss, higher installation cost, increased noise and power consumption, uneven cooling in the cooling space. For minimizing this problem, a proper design of duct is needed. Equal friction method is used to design the duct, which is simple method as compared with the other design methods. These work gives the combination of theoretical and software tool to provide a comparative analysis of the duct size. It also gives the comparison of pressure drop in rectangular duct and circular duct.

Keywords Equal friction method, friction loss, duct sizing

  1. INTRODUCTION

    There are many types of air conditioning system like window air conditioners, split air conditioners etc. but these ACs system are used in small room or office where cooling load required is low. When the cooling load required is very high like multiplex building, hospital etc. central ACs system are used. In central ACs system the cooled air is directly not distributed to the rooms. The cooled air from the air conditioning equipment must be properly distributed to rooms or spaces to be cold in order to provide comfort condition. When the cooled air cannot be supplied directly from the air conditioning equipment to the spaces to be cooled, then the ducts are installed. The duct systems convey the cold air from the air conditioning equipment to the proper air distribution point and also carry the return air from the

    room back to the air conditioning equipment for reconditioning and recirculation. In order to achieve required cooling load, proper method is required. Proper air distribution is achieved with proper duct design which leads minimum losses in the system, suitable selection of fan with high efficiency, optimum air velocity in duct, inlet and outlet of fan. Today some softwares are available to estimate cooling load, to design the duct. CFD and ANSYS software can be used for analysis of air motion and also can predict fluid characteristics and pressure differentials to a very low level that are experimentally impossible during experimentation. Analysis of air flow in duct with static pressure and velocity pressure is made easier and faster in fluent software. Various researchers are having there contribution on the topic. Design for high velocity duct system is done by determining the pressure losses, calculating the noise level, determining the out of balance pressures &optimizing this against the total cost of the system [1]. VAV optimization procedure was applied to the three VAV duct systems to investigate the impact of varying airflow rates on the sizing of duct systems. For comparison purposes, other duct design methods, such as, equal friction, static regain, and the Method, were also applied to the duct systems [2]. Design optimization of industrial ducts is achieved with CFD. The CFD analysis has offered a comprehensive range of output including velocity distribution, pressure profiles and turbulence levels. [3]

    Air may distribute in the room by air handling unit (AHU) or fan coil unit (FCU). The use of AHU and FCU is depends upon the cooling load required. In this work we decide that the FCU is used where cooling load required up to 5 tons and to use AHU above 5 tons. As we know that for FCU there is no duct is required. For calculating duct size first calculate the dehumidified air and there after duct dimension has to be calculated.

  2. THEORY

    The conditioned air (cooled or heated) from the air conditioning equipment must be properly distributed to rooms or spaces to be conditioned in order to provide comfort conditions. When the conditioned air cannot be supplied

    directly from the air conditioning equipment to the spaces to be conditioned, then the ducts are installed. The duct systems

    1. Duct area =

      air flow rate velocity

      convey the conditioned air from air conditioning equipment

      to proper air distribution points or air supply outlets in the room and carry there turn air from the room back to the air conditioning equipment for reconditioning and recirculation. The conditioned air (cooled or heated) from the air conditioning equipment must be properly distributed to rooms or spaces to be conditioned in order to provide comfort conditions. It may be noted that duct system for proper distribution of conditioned air cost nearly 20 to 30 % of total cost of equipment required. Duct material is usually made from galvanized iron sheet metal, Al sheet metal or black steel. But now a day, the use of non-metal ducts has increased. There sin bonded glass fiber ducts are used because they are quite strong and easy to manufacture according to desired shape and size. They are used in low velocity applications less than 600m/min and for static pressures below 5mm of water gauge. Iz of static pressure, dynamic pressure &total pressure in duct is important. The pressure in duct is usually expressed in mm of water. The pressure is lost due to friction between the moving particles of fluid (i.e. air) and interior surface of duct. When the pressure loss occurs in a straight duct, it is usually termed as friction loss. The pressure is also lost dynamically at the changes of direction such as in bends, elbows etc. and the changes of cross section of duct; this type of pressure loss is usually termed as dynamic loss.

      1. General rules for duct design

        • Air should be conveyed as directly as possible to economize on power, material and shape.

        • Sudden change in direction should be avoided.

        • Air velocities in ducts should be within the permissible limits to minimize losses.

        • Rectangular ducts should be made as nearly square as possible. This will ensure minimum ducts surface. An aspect ratio of less than 4:1 should be maintained.

        • Damper should be provided in each branch outlet for balancing the system.

  3. METHOD OF DUCT DESIGN

        1. Equal friction method

        2. Velocity reduction method

        3. Static reduction method

    In Equal Friction Method the frictional presure dropper unit length of the duct is maintained constant throughout the duct system. Due to its simplicity, this method is used in the thesis to design the duct.

    1. Calculation for duct size/dimension

      1. First find out the air flow rate i.e. dehumidified air and cooling load.

      2. Based on cooling load select AHU or FCU which is to be installed. For FCU there is no need to duct system. If AHU then calculate the duct dimension.

      3. Select initial velocity (from CarrierHandbook)

        5. Based on duct area select duct size/dimension (From Carrier Handbook), also Equivalent duct diameter.

        Then initial friction rate is determined by using friction chart, on the basis of air quantity and equivalent duct diameter or velocity of air.

    2. Calculation for dehumidified air quantity

    Room Rise = (1 by pass factor)*(Room temp – ADP) Dehumidified Air = RSH / (20.44 * dehumidified rise) Where,

    ADP = apparatus due point RSH = room sensible heat

  4. RESULT

    To design the duct for TIIR building calculation of cooling load and air flow rate is done. By taking some suitable velocity (from Table 1), considering noise factor main duct area is calculated. Based on these duct area, the duct size is find out for the rectangular duct as well as round duct. The cooling load, dehumidified air flow, duct size for all room is given in below:

    TABLE-I COOLING LOAD AND DEHUMIDIFIED AIR FOR RESPECTIVE ROOM

    S.N.

    Room Name

    Cooling Load (tons)

    Dehumidified Air Flow (m3/min)

    Type of unit used (FCU/AHU)

    1

    120 seat Lecture Room 1

    12.39

    113

    AHU

    2

    Direct TIIR

    2.11

    21

    FCU

    3

    Admin Office

    3.03

    32

    FCU

    4

    Placement Office

    2.27

    25

    FCU

    5

    IPR Office

    2.93

    32

    FCU

    6

    120 seat Lecture Room 2

    12.39

    113

    AHU

    7

    Office Room

    6.96

    69

    AHU

    8

    Meeting Room

    6.77

    66

    AHU

    9

    Library

    4.53

    43

    FCU

    10

    Dining

    5.85

    63

    AHU

    11

    Alumini Relation

    4.68

    49

    FCU

    12

    Alumini Visitor

    7.55

    74

    AHU

    13

    Interview Room 1

    2.95

    31

    FCU

    14

    Interview Room 2

    4.69

    44

    FCU

    15

    Seminar Room

    7.16

    69

    AHU

    16

    Central Design Office

    24.69

    247

    AHU

    17

    Auditorium

    50.14

    422

    AHU

    18

    Library Facility

    5.57

    48

    AHU

    Ansys 13.0 is used to observe the friction loss in rectangular duct as well as circular duct. For analysis we select only small portion of duct (3 m), also it can be applied

    for all ducting in a building. It can be easily noticed that the friction loss in rectangular duct is greater than the circular duct.

    Figure-1 Pressure Variation along with Length in Rectangular Duct

    Figure-2 Pressure Variation along with Length in Circular Duct

  5. CONCLUSION

  1. The duct design for TIIR building is done, by using equal friction method. All values are comparable with the value find by duct software called ductulator.

  2. The calculated value of frictional is less or near as calculated by software. Due to less value of friction drop, duct diameter is increased but loss in total pressure (i.e. static pressure, velocity pressure) can be avoided. Also use of damper may be decreased.

  3. Ansys 13.0 software is used to analyze the pressure loss in circular and rectangular duct. After analysis we conclude that the circular duct has minimum friction loss, so it is better shape for ducting.

  4. The circular duct can carry more air in less space, because of that, less duct material, less duct surface friction and less insulation is required.

REFERENCES

  1. G.S. Sharma and B. Sharma. Duct designing in air conditioning system and its impact on system performance. VSRD International Journal of Mechanical, Automobile and Production Engineering, Vol. 2 No. 9 November 2012.

  2. Kim, Taecheol.,andSpitler, J.D.,Optimization of VAV Duct System, ASHRAE transactions 2002, vol.108, part-I, pp. 96-104.

  3. RavirajGurav, Sanjay Gaikwad,PriteePurohit. Duct Design using equal friction method & CFD. International conference on recent technology 2012.

  4. Air distribution. Carrier air conditioning company, Carrier handbook of air conditioning and air refrigeration.

TABLE II DUCT SIZE COMPARISON BETWEEN HAND CALCULATION AND DUCTULATOR SOFTWARE

S.N.

Room

Hand calculation

Using software (ductulator)

Rectangular duct (mm)

Round duct (mm)

Friction drop

Rectangular duct (mm)

Round duct (mm)

Friction drop

1

120 seat lecture room 1

650 * 600

680

0.0445

700 * 550

675

0.0487

2

Direct TIIR

FCU is used, no ducting is required

3

Admin Office

FCU is used, no ducting is required

4

Placement office

FCU is used, no ducting is required

5

IPR Office

FCU is used, no ducting is required

6

120 seat lecture room 2

650 * 600

680

0.0445

700 * 550

675

0.0487

7

Office Room

600 * 400

530

0.0600

550 * 450

525

0.0655

8

Meeting Room

500 * 450

520

0.0630

500 * 450

520

0.0674

9

Library

FCU is used, no ducting is required

10

Dining

550 * 400

510

0.0663

500 * 450

500

0.0694

11

Alumini Relation

FCU is used, no ducting is required

12

Alumini Visitor

550 * 500

570

0.0603

550 * 450

550

0.0627

13

Interview Room 1/p>

FCU is used, no ducting is required

14

Interview Room 2

FCU is used, no ducting is required

15

Seminar Room

600 * 400

530

0.0623

550 * 450

530

0.0655

16

Central Design Office

950 * 900

1000

0.0295

1000 * 850

1000

0.0303

17

Auditorium

1200*1200

1300

0.0195

1250*1150

1300

0.0220

18

Library Facility

450 * 400

460

0.0792

450 * 400

460

0.0822