🔒
Trusted Engineering Publisher
Serving Researchers Since 2012

Analysis on Mix Design of High Strength Concrete [M55 & M70]

DOI : https://doi.org/10.5281/zenodo.19945614
Download Full-Text PDF Cite this Publication

Text Only Version

Analysis on Mix Design of High Strength Concrete [M55 & M70]

Pratyush Mishra

Undergraduate Student, Department of Civil Engineering, Bhilai Institute of Technology, Durg, India

Prakhar Kumar Sahu

Undergraduate Student, Department of Civil Engineering, Bhilai Institute of Technology, Durg, India

Mr. Sumit Gupta

Assistant Professor Department of Civil Engineeering, Bhilai Institute of Technology, Durg, India

Prahar Chandrakar

Undergraduate Student, Department of Civil Engineering, Bhilai Institute of Technology, Durg, India

Yashita Shrivastava

Undergraduate Student, Department of Civil Engineering, Bhilai Institute of Technology, Durg, India

Abstract – This research paper is based on study in performance improvement of high-strength concrete. Initially, a conventional concrete of three cube specimens of size 150mm x 150mm x 150mm of M55 grade with water cement ratio of 0.35 were casted and tested after 28 days of curing, yielding an compressive strength of 43.11 MPa, 43.6 MPa, 42.88 MPa and average compressive strength of 43.19 MPa, which is lower than target strength. So to overcome this, a modified mix design of M70 grade concrete with water cement ratio 0.27 was made by adding silica fume 5% and fly ash 15% as a supplementary cementitious material. Together, two cube specimen of size 150mm x 150mm x 150mm and two beam specimen of size 150mm x 150mm x 700mm were casted using modified mix. The 7-day and 28-day compressive strength of cube comes out to be 43.6 MPa and 79.9 MPa, exceeding the target strength, indicates increase in mechanical properties. Flexural strength tests were conducted on overhanging beam under centre point loading, and result of beam comes out to be 6.98 MPa and 10.46 MPa, the average flexural strength of two beam was 8.72 MPa. Further, comparison of the two beam was carried using structural analysis software SAP 2000, and support reaction, shear force, bending moment, deflection diagram were made. Most of the results were in accordance with the standards but as experimental test provides real behavior, and software analysis predicts theoretical results so both the results have some deviations.

Keywords High strength concrete; Silica fume; Fly ash; Compressive strength; Flexural strength; SAP 2000.

  1. INTRODUCTION

    High strength concrete has a compressive strength greater than 55 MPa having water cement ratio (w/c) ranging from 0.35 to

    0.27 or even less. Due to low w/c ratio it requires mineral admixtures such as silica fumes and fly ash as a partial replacement of cement, it also requires a polycarboxylate ether based super plasticizer such as aura-mix 300 to improve workability, reduce water content, and enhance strength. For high strength concrete (M 55 or above) mixes, generally OPC-53 grade cement is used. In this study, mix design for M55

    concrete cube specimen and M70 concrete cube and beam specimen are carried out. Then, the cube was tested on compressive testing machine and beam with centre point loading on flexural testing machine after 7 and 28 days of curing. Thereafter, on the basis of centre point loading, the failure load of two beams were analysed and compared in software SAP 2000 and getting the values of support reaction, shear force, bending moment, and deflection.

    High strength concrete can be used for various applications such as pre-cast railway sleeper, high rise buildings, bridge construction etc.

  2. MATERIALS AND METHODS

    1. Materials used

      1. Cement-In this study, Ultra Tech OPC 53 grade cement is used and color of cement is grey. Specific gravity of the cement is 3.15.

      2. Fine aggregate- River sand is used as fine aggregate. Specific gravity of the fine aggregate is 2.65.

      3. Coarse Aggregate- Stones made from Crushed rocks are used as coarse aggregate. Specific gravity of the coarse aggregate is 2.74.

      4. Silica Fume- Sika Fume DS is used. It is dark grey to greyish black powder in color with specific gravity of 2.20.

      5. Water- The curing tank or while casting of specimens the water should be free from any dirt or harmful chemicals. As, water cement ratio is important for strength evaluation of concrete.

      6. Fly ash- Fly ash used was procured from a local brick manufacturing unit. It is dark grey to almost black in colour with specific gravity of 2.20.

      7. Superplasticizer- Auramix 300 (polycarboxylate ether based) manufactured by Fosroc chemicals India Pvt. Ltd is used, is a high range water reducing admixture used to improve workability without increasing water content with a relatively low dosage 0.5% by cement weight with specific gravity of

        1.08 is used.

    2. Procedure

      1. Initially 3 cubes of size 150 x 150 x 150 mm of conventional high strength M55 grade is casted without mineral admixture and put for 28 days of curing.

      2. Thereafter, 2 cube and 2 beam specimen of size 150 x 150 x 700 mm were casted by adding 5% silica fume and 15% fly ash. The cube specimen was tested after 7 and 28 days of curing and beam after 28 days of curing.

        The steps are shown in following figures-

        Fig.1 Mixing of concrete

        cube 1

        cube 2

        cube 3

        Avg

        Fig. 2 Concrete filled in mould

        Silica fume

        1.02 Kg

        Fly Ash

        3.061 Kg

        Water / Cement

        Ratio

        0.35

        .27

        C : FA : CA

        1 : 1.60 : 3.03

        1 : 1.37 : 2.84

  3. TEST AND RESULTS

        1. The 28-day compressive test result for conventional M55 grade concrete was shown in following table and graph:

          Table 2. Compressive test result M55

          Age in days

          28

          No of Cubes

          3

          Cube Strength

          in MPa

          Cube 1

          43.11

          Cube 2

          43.6

          Cube 3

          42.88

          Average compressive strength

          in MPa

          43.19

          43.8

          43.6

          43.4

          43.2

          43

          42.8

          42.6

          42.4

          Compressive

          strength after 28 days

          Average strength

          No .of Cubes

          Compressive strength

          ( in MPa)

          Graph 1. Compressive strength comparison M55

          Fig. 3 Curing for 7 and 28 days

          C. IX DESIGN

          1. Mix design for conventional M 55 and modified mix M70 grade. For the calculations of the quantities and mix design different research paper and literature review were used.

          Table 1. Mix design for M 55 and M70

        2. The 7 and 28 day compressive test result for modified mix M70 grade concrete was shown in following table and graph:

          Age in days

          7

          28

          No of Cubes

          1

          Cube strength

          in MPa

          Cube 1

          43.6

          Cube 2

          79.9

          Average compressive strength

          in MPa

          43.6

          79.9

          Table 3. Compressive test result M70

          Ingredients

          F r 3 cubes M55

          For 2 cubes + 2 beams M70

          Cement

          4.17 Kg

          16.36 Kg

          Water

          1.46 L

          5.39 L

          Fine Aggregate

          6.69 Kg

          22.52 Kg

          Coarse Aggregate

          12.66 Kg

          46.61 Kg

          Chemical Admixture

          20 Ml

          84.11Ml

          100

          80

          60

          40

          20

          0

          Compressive

          strength after 7 days

          Compressive strength after 28 days

          No.of cubes

          Compressive Strength

          (in MPa)

          Graph 2. Compressive strength comparison M70

        3. The 28 day flexural strength of 2 beams under centre point loading were shown in following tables and graph:

          Width and depth

          b, d (mm)

          Weight

          (Kg)

          Dial Reading, 1 Division

          =1000kg

          Beam No

          39

          Span length L(mm)

          400

          1

          150

          2

          6

          39.2

          400

          150

          Table 4. Beam experimental data

          0.46

58.86

8.72

.98

39.24

Average strength (MPa)

Flexural strength ,

Fb

(MPa) Fb = 3PL /

2bd2

Load at failure P (KN)

Table 5. Beam flexural test result

Flexural strength (in MPa)

Beam 1

Beam 2

Avg

Graph 3. Flexural strength comparison

      1. Software analysis SAP 2000 result:

        1. Beam 1 (at centre point load 39.24 KN)

          Fig. 4 Support reaction beam 1

          Fig. 5 Shear force beam 1

          12

          10

          8

          6

          4

          2

          0

          Flexural strength

          after 28 days

          Average strength

          No of beams

          Fig. 6 Bending moment beam 1

          Fig. 7 Deflection beam 1

          Fig. 8 SFD, BMD, Deflection maximum beam 1

        2. Beam 2 (at centre point load 58.86 KN)

Fig. 9 Support reaction beam 2

Fig. 10 Shear force beam 2

Fig. 11 Bending moment beam 2

Fig. 12 Deflection beam 2

Fig. 13 SFD, BMD, Deflection maximum beam

  1. CONCLUSION

The average compressive result of cube after 28 days for M55 and M70 grade was 43.19MPa and 79.9 MPa and flexural result of 2 beams was 8.72 MPa. It shows that M55 mix is insufficient for high strength concrete as it is lower than target strength, whereas modified mix M70 shows excellent performance in terms of compression and flexural. Analysis of SAP 2000 indicates that maximum bending moment and deflection occurs at mid span of the beam.

REFERENCES

  1. M. Amin, K. Abu el-Hassan, M. Shaaban, A.A Mashaly, ” Effect of waste tea ash and sugar beet waste ash on green high strength concrete”, Construction and building materials, vol. 495, pp.143611, October 2025.

  2. A.R. Hariharan. A.S. SANTZHZI,Z”Study on strength development of high

    strength concrete containing fly ash and silica fume”, International Journal of Engineering Science and Technology, vol.3, pp. 3925-3932, May 2011.

  3. M. Amin, A.M. Zeyad. I.S. Agwa, A.M. Heniegal, “Effect of peanut and sunflower shell ash on properties of sustainable high-strength concrete”, Journal of Building Engineering, vol. 89, pp. 109208, July 2024.

  4. F.A. Mustapha, A. Sulaiman, R.N. Mohamed, S.A. Umara, “The effect of fly ash and silica fume on self-compacting high-performance concrete”, Materials Today: Proceedings, vol.39, pp.965-969, January 2021.

  5. S. Pyo, H.Yoo, ” Influence of flexural testing parameters on the flexural response of ultra-high-performance concrete”, Materials and Structures, vol.49. pp.3655-3668, September 2016.

  6. T. Balaji, T.M. Jeyashree, P.R. Kannan Rajkumar, J. Baskara Sundararaj, M.Jegan,” Effect of elevated temperature on concrete incorporating zeolite, silica fume and fly ash as replacement of cement”, Research on engineering structures and materials, vol.11, pp.1245-1258, September 2025.