Thermal Requirements of A Residential Apartment Building Through Natural Ventilation in the Warm and Humid Climate of Guwahati

DOI : 10.17577/IJERTV9IS060952

Download Full-Text PDF Cite this Publication

Text Only Version

Thermal Requirements of A Residential Apartment Building Through Natural Ventilation in the Warm and Humid Climate of Guwahati

Amal Barman Department of Architecture Jadavpur University Kolkata, India

Dr. Arpan Dasgupta Department of Architecture Amity University

Kolkata, India

Dr. Madhumita Roy Department of Architecture Jadavpur University Kolkata, India

Abstract Natural resources that can provide better thermal comfort condition in warm and humid climate are natural ventilation and better shading performances. The effectiveness of natural ventilation and shading performance is determined by prevailing outdoor microclimate conditions and surrounding building envelops. This study investigates the thermal comfort performance in medium-rise residential apartment building through natural ventilation approach. This study was conducted at national games village, a G+6 storied residential apartment complex of Guwahati. Computer simulation is done using ENVI MET 4.0 microclimate software to calculate the parameters of air temperature, relative humidity, wind speed and surface temperature surfaces. After analysing the data's of each condition, the Predicted Mean Vote (PMV) has been obtained by using ENVI MET 4.0. The result shows that optimum WFR of 16.65% as proposed by GMDA bye-laws is not sufficient to lower air temperature as compared to the outside ambient temperature. However, in the case of applying natural ventilation strategies, comfort condition is achieved at night only.

Keywords Natural ventilation, thermal comfort, Warm and humid climate, building form

  1. INTRODUCTION

    In recent time, the concept of sustainability has influenced the entire building industry in such a way that the futuristic approach of every single building has to be more climate- responsive. Due to the growing use of active ventilation system in the warm and humid climate of Guwahati, there is excessive use of energy in the building. Emission of a high percentage of greenhouse gases from these high energy building creates an uncomfortable outdoor thermal condition, especially in summer months. This growing problem is leading to a demand for the use of passive strategies for indoor climate modification. In a warm and humid climatic zone, Guwahati experiences a high daytime temperature of around 29o to 34o Celsius during summer and high relative humidity of 65% to 95%. The building structures are also exposed to a high intensity of solar radiation and penetration. This uncomfortable situation has lead to the use of air- conditioner as a compulsory alternative in almost every household of Guwahati to adjust the room temperature to the preferred level. This approach of using air conditioner

    becomes the main influential factor of high energy consumption in a building which contributes to a massive negative impact on the environment. As a green initiative to this problem, effective use of natural ventilation can be a suitable option for prevention of overheating and indoor climate modification since Guwahati has a 13.6% natural ventilation potential. Optimum use of natural ventilation can maximize its effects on thermal mass in reducing the indoor temperature in buildings up to a great extent. In the urban scale of neighbourhood planning, one of the design strategies that have the potential to overcome this climatic problem is the formation of a cluster of building around a central open space. A central open space is an enclosed area surrounded by adjoining building blocks and has opened to the sky in a housing complex. This planning concept can be well applied in the warm and humid climatic zone because it offers air exchange between hot and cool air during day and night. With proper orientation of building blocks, composition, and effective airflow pattern can be channelised to the central open space the first objective of this study is to investigate the performance of indoor air temperature compared to the ambient level. The purpose is to find significance on the difference in air temperature between ambient level and indoor due to the building design. The second objective is to investigate the performance of a natural ventilation approach to the indoor thermal condition. This objective will analyze the outdoor air temperature profile that influences the indoor room temperature and comfort level.

  2. BIO CLIMATIC FACTORS AND DEVELOPMENT CONTROL RULES OF GUWAHATI

Fig. 2.1: Bio-climatic chart for Guwahati(Singp007)

Guwahati is located at a latitude of 26°1445N, the longitude of 91°7263E and altitude of 54 m above sea level. This city has an annual average temperature of 24.21°C and relative humidity remains above 70% most of the time throughout the year. Prevailing wind direction is from SW to NE in summer with an average velocity of 6.9 m/s and from NE to SW in winter with an average velocity of 5.47 m/s (Table 2.3). The bio-climatic data of Guwahati project Comfort condition for about 14.17% time of the year in the winter and early summer months, whereas it shows that Conventional air-conditioning is required for 53.75% time of the year due to high humid climate during summer months. The usability of Natural Ventilation is about 16.7% time of the year. These figures represent the potential energy usage and potential energy savings depending upon the building design, orientation, and surrounding developments.

Regional Climate of Guwahati depends on Seasonal air temperatures, annual rainfall, Relative humidity and prevailing wind velocity and directions as per meteorological data of the city (Table.2.3).

Table.2.3: Meteorological data of Guwahati from Sept. 2018 to August 2019 (Source: Weatheronline.com)

Month

Rainfall (mm)

Air Temperature

Wind Speed Avg (Km/h)

Wind Direction

RH (%)

Max.

Min.

Sept. 2018

179.72

31

24

4.2

W,SW

81%

Oct. 2018

148.70

30

21

5.1

E,SE,NE

74%

Nov. 2018

16.20

27

18

5.4

E,SE,NE

71%

Dec. 2018

62.6

24

15

5.4

E,SE,NE

70%

Jan. 2019

3.90

25

15

5.8

E,SE,NE

57%

Feb. 2019

48.90

27

16

6.9

E,SE,NW

59%

Mar. 2019

22.70

31

19

7.9

E,SE,SW

46%

April 2019

224.20

34

23

7.4

E,SE,SW

57%

May 2019

639.60

34

24

8.6

E,SE,SW

73%

June 2019

536.80

35

26

5.2

W,SW

74%

July 2019

1172.60

32

25

6.3

W,SW

85%

August 2019

694.00

34

27

6.0

W,SW

78%

  1. Urban design regulations in Guwahati

    Urban design in Guwahati is governed by GMDA Building bye-laws and Guwahati Master Plan Zoning for the year 2025. The land-use zones contain residential areas, commercial areas, industrial areas, and Public/Semi-public areas. GMDA bye-laws specify the maximum number of floors, maximum building heights, road widths, building percentage (plot/ground coverage), floor area ratio (FAR), setbacks, etc.

    1. Residential apartment buildings in Guwahati

      The areas designated for residential use in Guwahati are divided into four distinguished plot typology of A, B, C, and D (Table 2.1.1). The minimum plot sizes for different residential sectors vary between below 670 m² (sector A) to above 6670 m² (sector D). The provisions regarding plot coverage, number of floors, building height, setbacks and the maximum FAR for each sector are shown in Table 2.1.1.

      Table 2.1.1: GMDA bye-law provisions for residential use A, B, C and D

      Reside ntial plot type

      Road Width (m)

      Max. plot covera ge

      Max. no. of floors

      Ma x FA R

      Max. Heigh t (m)

      Setback (m)

      Fron t

      Bac k

      Side s

      A

      (up to 670

      Sqm)

      3.6 to 4.5

      60%

      G+2

      1.0

      0

      9.6

      3.6

      1.8

      1.8

      4.5 to 6.6

      60%

      G+3

      1.2

      5

      12.6

      4.5

      2.4

      2.4

      6.6 to 8.0

      55%

      G+4

      1.5

      0

      15.6

      6.0

      3.6

      3.6

      8.0 to 15.0

      50%

      G+4

      1.5

      0

      15.6

      6.0

      3.6

      3.6

      Above 15.0

      50%

      G+5

      1.7

      5

      18.6

      9.0

      4.2

      4.2

      B

      (above 670 to

      1338

      sqm)

      3.6 to 4.5

      50%

      G+2

      1.0

      0

      9.6

      3.6

      1.8

      1.8

      4.5 to 6.6

      50%

      G+4

      1.2

      5

      15.6

      4.5

      3.6

      3.6

      6.6 to 8.0

      50%

      G+4

      1.6

      0

      18.6

      9.0

      4.2

      4.2

      8.0 to 15.0

      45%

      G+8

      1.7

      5

      27.6

      9.0

      6.0

      6.0

      Above 15.0

      40%

      G+8

      1.7

      5

      27.6

      =9.0

      <

      6.0

      6.0

      C

      (above 1338 to

      6690

      sqm)

      3.6 to 4.5

      50%

      G+2

      1.2

      5

      9.6

      3.6

      1.8

      1.8

      4.5 to 6.6

      50%

      G+5

      1.2

      5

      18.6

      9.0

      4.2

      4.2

      6.6 to 8.0

      45%

      G+7

      1.7

      5

      24.6

      9.0

      5.5

      5.5

      8.0 to 15.0

      40%

      No Limit

      2.2

      5

      No Limit

      9.0

      =7.0

      <

      =7.0

      <

      Above 15.0

      40%

      No Limit

      2.2

      5

      No Limit

      =9.0

      <

      =7.0

      <

      =7.0

      <

      D

      (above 6690

      sqm)

      3.6 to 4.5

      45%

      G+3

      1.2

      5

      12.6

      4.5

      2.4

      2.4

      4.5 to 6.6

      45%

      G+5

      1.5

      0

      18.6

      9.0

      4.2

      4.2

      6.6 to 8.0

      40%

      G+7

      1.7

      5

      24.6

      9.0

      5.5

      5.5

      8.0 to 15.0

      40%

      No Limit

      2.2

      5

      No Limit

      9.0

      =7.0

      <

      =7.0

      <

      Above 15.0

      40%

      No Limit

      2.5

      0

      No Limit

      =9.0

      <

      =7.0

      <

      =7.0

      <

      The Residential apartment buildings in Guwahati are designated to develop in the plot typology of B, C, and D. The Residential apartment buildings are Naturally Ventilated since existing GMDA building bye-law strictly follows rules to provide minimum 16.67% WFR in every habitable room. All the habitable rooms should face at least one external wall or ventilation shaft wall with a minimum size of 3.0m x 3.0m. Natural ventilation is achieved by providing windows. Information on ventilation rate is needed when calculating the energy use of a building. In Guwahati, there is very little knowledge of the actual ventilation rate in apartments. Therefore, the ventilation rate is measured in a typical apartment.

    2. Natural ventilation in warm and humid climate of Guwahati

      The most common element of natural ventilation is openings in facades (windows). The keys to effective natural ventilation are the building orientation, the size and placing of the window openings. For buildings in warm-humid climates, it is recommended to create openings in different

      walls to allow cross ventilation for all rooms. This will enable the free flow of air throughout the building. Window sizes and location would determine the success of the ventilation strategy in a building. The openings on either side of the building enable cross-ventilation by creating different pressure zones. The size, location and orientation of these openings will affect the airflow inside the building. Therefore, the average interior air velocity depends on the size and location of the openings, the angle between the wind direction and the opening, and exterior wind velocity. Acceptable interior airflow depends on the temperature and humidity of the environment. At temperatures below 33C, an increase in air velocity increases the thermal comfort level.

      During summer, in a typical warm and humid climate of Guwahati, thermal comfort can be achieved by the following aspects. Firstly, when the outside temperature is lower than the indoor temperature, ventilation can cool down the indoor air by replacing with the outside air. It also cools down the building structure. The second aspect is when the outside temperature is higher; ventilation can cause direct cooling on the human body by evaporation and convection.

    3. Physical parameters of thermal comfort in warm and humid climate

      According to ASHRAE, thermal comfort is defined as the "condition of mind that expresses satisfaction with the thermal environment" (ASHRAE, 1997). In warm and huid climate of Guwahati, the air temperature ranges from 24o to 30°C and the relative humidity from 70 to 99 %. The thermal comfort indicator are generally based on prediction of percentage dissatisfied (PPD) and predicted mean value (PMV). PMV is an index that predicts the mean value of the votes of a large group of persons on seven thermal sensation scales while PPD is an index which shows a quantity prediction of the percentage of thermally dissatisfied people determined from PMV. PMV is the most reliable thermal comfort index. It has proven to provide reliable results for thermal environments close to thermal comfort. The PMV values vary from 3 to +3 according to the thermal sensation scale in Table 2.1.4.1 These standards are assumed as universal and thus applicable for every building types, every climatic zones and every populations.

      Most of the common thermal indices for indoor conditions are based on this heat balance of the human body (McIntyre, 1980). There are four climatic factors influence the thermal comfort of the human body.

      1. Air temperature: Increasing air temperature decreases the bodys convective heat loss and its dry respiration heat loss influencing thermal comfort.

      2. Radiation: The absorption of solar radiation and the exchange of long-wave radiation from room surfaces strongly affect the state of thermal comfort of the human body in indoor conditions. It is expressed in the form of MRT.

      3. Humidity: A change in the humidity of the atmosphere affects thermal sensation in that a person feels warmer, sweatier and uncomfortable. Especially in warm conditions, when both convective heat and radiative heat losses are small, sweat evaporation is an important mechanism in maintaining thermal comfort.

      4. Wind speed: Increasing air speed increases the convection heat loss and the evaporation of sweat Strong affecting the state of thermal comfort of human body. air movement is thus a clear advantage in warm and humid climates.

    4. Thermal comfort standards

The thermal comfort standards in the world are ISO 7730 and ASHRAE 55. The most common thermal comfort standard is based on the PMV index. The thermal sensation scale of PMV in Table2.1.4.1. The comfort zone of PMV is defined as: 0.5 PMV +0.5. This comfort zone is suitable for both summer and winter.

Table 2.1.4.1 Thermal Sensation scale for PMV index

Sensation

Cold

Cool

Slightly Cool

Neutral

Slightly Warm

Warm

Hot

PMV

-3

-2

-1

0

1

2

3

The ASHRAE comfort standard 55 has one comfort zone for the summer and another for the winter. The activity, clothing and air speed for the summer and winter comfort zones are shown in Table 2.1.4.2. It is thus assumed that in summer the clothing insulation is less and the air speed higher than in winter.

Table 2.1.4.2 Parameters for the summer and winter Comfort zones of ASHRAE comfort standard 55

Parameters

Summer

Winter

Activity

1.2 met

1.2 met

Clothing

0.5 clo

0.5 clo

Air speed

.25 m/s

.15 m/s

  1. METHODOLOGY

    1. Investigated base Case study area: National Games Village, Borsajai, Guwahati

      Based on the GMDA building bye-laws and development regulations regarding building heights, street widths and setbacks, an existing model urban area of a residential neighbourhood of National Games Village (Fig. 3.1.1) at Borsajai, Guwahati is selected for Microclimate simulations. The campus was developed by GMDA as a group housing scheme in the year 2007. 616 apartments were sold to individual middle-income group families. Present population is approximately 3080 with a density of 132 apartments/hectare. The entire development is based on Type D residential sector. The base case study area is a simplified cluster of typical geometric patterns, material properties, facade colours and ground elements. , the head margin in this template measures proportionately more than is customary. This measurement and others are deliberate, using specifications that anticipate your paper as one part of the entire proceedings, and not as an independent document. Please do not revise any of the current designations.

      Fig. 3.1.1: satellite map of case study area of National games Village, Borsajai, Guwahati.

      Fig. 3.1.2: Master Plan of Residential neighbourhood of National games Village, Borsajai, Guwahati.

      The southern part of the model cluster consists of two rows of plots with six plots on each side of a 6.6 wide road with a 40m wide right of way (Fig. 6.4.3) in E-W direction. The buildings are 21.6 m high (G+6 floors). The road width is

      6.6 m within the stipulated minimum width of 6.6 m to 8.0m. The setbacks are in accordance with the development regulations (front = 9.0 rear setbacks = 6.0 m, side setbacks =

      4.0 m). This results in the street height-to-width ratio (H/W) of 0.54, 0.92, 1.56 and 2.70. The base model has no vegetation.

      Table 3.1.1: Input data for the summer and winter base case simulations

      Variables/Description

      Summer

      Winter

      Building height, H (m)

      21.6

      21.6

      Distance between buildings, W (m)

      40,23.5,13.8, 8

      40,23.5,13.8,8

      H/W ratio

      0.54,0.92,1.56,2.7

      0.54,0.92,1.56,2.7

      Wind speed (at 1.5 m height) (m/s)

      3.0

      4.0

      Max. Indoor temperature (°C)

      33

      22

      U-value, walls (W/m²°C)

      2.77

      2.77

      U-value, roof (W/m²°C)

      2.49

      2.49

      Reflectivity, facades

      0.40

      0.40

      Reflectivity, roofs

      0.25

      0.25

      Reflectivity, street, surface

      0.25

      0.25

      Clothing value (for PMV calculation)

      0.9

      1.5

      Guwahati has a warm and humid summer and a dry cold winter, whereas both spring and autumn are quite comfortable. Two base cases are shaped, one for the summer and other for the winter. The summer is represented by 21 June and the winter by 22 December. The input data of the base cases are shown in Table 3.1.1.

      Fig. 3.1.2: section of the model area of the base case with H/W ratio of 0.92, 1.56, 2.70 in N-S direction

      Fig. 3.1.3: section of the model area of the base case with H/W ratio of 0.54 in E-W direction.

    2. Instrumentation

      In this experiment, the equipments that have been used are the Digital Anemometer to measure the wind speed in indoor and outdoor conditions, Max – Min Thermo Hygro – Clock TA218B to measure temperature and relative humidity in indoor and outdoor conditions. Both Max – Min Thermo Hygro – Clock TA218B and Digital Anemometer has hygrometer, thermometer, clock, and anemometer device integrated with it. Digital Anemometer has accuracy for wind speed about ± 5%, and Max – Min Thermo Hygro – Clock TA218B has an accuracy of air temperature about ± 1.2 oC and relative humidity of ± 4%. Both Max – Min Thermo Hygro – Clock TA218B and Digital Anemometer has been used as portable measurement device. Both the equipments are used by placing at 0.6 to 0.9 meter from floor. For outdoor thermal comfort analysis, Envi Met 4.0 micro climate simulatio software is used to find out the PMV level and wind velocity where as Design Builder Energy Plus program has been used to predict the room thermal comfort condition .

      Fig. 3.2.1: Digital Thermo & Hygrometer, Digital Anemometer

    3. Data collection

      The collection of measurement data consists of three main locations which are the outdoor environment that is located outside the building perimeter, the central open space and the selected indoor rooms. The data taken are air

      temperature, relative humidity, and wind speed. Envi-met simulation data is used for surface temperature and PMV.

      The purpose is to find overall temperature modification in the central open space while the other points are to get the air velocity and temperature from different external window opening of the various rooms which offers cross ventilation through the building. The ambient temperature is measured by selected outdoor position which is put outside the building perimeter to get the thermal and wind modification of the surrounding area.

      The measured data are air temperature, wind speed infiltration through the windows and door and the relative humidity level. The data that has been measured by the Max – Min Thermo Hygro – Clock TA218B and digital anemometer portable unit devices which are indoor air temperature, relative humidity and indoor air speed. All the positions are based on the procedure in ASHRAE standard 55p, 2003.

    4. Measurement position

    The measurement for the indoor position is conducted at

    1.1 m height from floor level at all points. It is the same height for the measurement of the outdoor location and courtyard. It is decided to be 1.1m because of consideration of human activities like sitting and standing. According to ASHRAE standard 55p, air temperature and air speed shall be measured at the 0.6, and 1.1m.

  2. MICROCLIMATE SIMULATIONS

To study the thermal impacts of these different parameters, the thermal simulation software ENVI MET 4.0 for outdoor micro climate simulation and Design-Builder Energy Plus is used for indoor simulation. The software ENVI-met, version 4.0 combines the calculation of fluid dynamics parameters such as wind flow and turbulence with the thermodynamic processes taking place on the ground surfaces, walls, roofs and in the vegetation.

  1. Outdoor Air temperature

    Fig. 4.1.1: Simulation results of air temperature at 1.00pm the summer day (21 June) at a height of 900mm from GL.

    The simulated outdoor air temperatures are shown in Fig. 4.1.1 (summer) and Fig. 4.1.2 (winter). In general, the air temperature does not vary much between the cases. However the increase of the H/W ratio leads to a decrease in maximum

    air temperature (at around 1.00 pm), but this decrease is small (< 1°C in summer and < 0.5°C in winter). In the summer, the biggest decrease is achieved by using trees and higher reflectivity of the pavements and roads.

    Fig. 4.1.2: Simulation results of air temperature at 1.00pm the winter day (22 December) at a height of 900mm from GL.

  2. Outdoor Relative Humidity

    Fig. 4.2.1: Simulation results of Relative Humidity at 1.00pm the Summer day (21 June) at a height of 900mm from GL.

    Fig. 4.2.2: Simulation results of air temperature at 1.00pm the winter day (22 December) at a height of 900mm from GL.

    The simulated outdoor Relative Humidity is shown in Fig. 4.2.1 (summer) and Fig. 4.2.2 (winter). In general, the Relative Humidity does not vary much between the cases. However the increase of the H/W ratio leads to a decrease in maximum Relative Humidity (at around 1.00 pm), but this

    decrease is small (1-2% in summer and 3-4% in winter). In the summer, the biggest decrease is achieved along the wider pavements and roads.

  3. Outdoor Wind Speed

    Fig. 4.3.1: Simulation results of Wind speed at 1.00pm the Summer day (21 June) at a height of 900mm from GL.

    The simulated outdoor Wind velocity at various points inside the residential complex is shown in Fig. 4.3.1 (summer) and Fig. 4.3.2 (winter). In the summer, the wind velocity around the blocks varies between 1.73 m/s to 4.31 m/s where H/W ratio < 1 and wind speed is 5.15 m/s when H/W ratio >1. In the winter, the wind velocity around the blocks varies between 1.30 m/s to 3.30 m/s where H/W ratio

    < 1 and wind speed is 4.55 m/s when H/W ratio >1. In both summer and winter, increase in H/W ratio leads to the increase in wind speed.

    Fig. 4.3.2: Simulation results of wind speed at 1.00pm the winter day (22 December) at a height of 900mm from GL.

  4. Outdoor thermal comfort

    The outdoor thermal comfort expressed as the PMV index is shown for some of the cases in both summer (Fig. 4.4.1) and winter (Fig. 4.4.2). The PMV in its outdoor version of ENVI-met 4.0 is able summarise the effects of air temperature, MRT, humidity, and wind on the persons energy balance in one value each of it weighted with level of influence. The results are shown for 1 pm in both summer and winter when the solar radiation is significant. In the summer, the height of building shades creates some shading which improves the thermal comfort for pedestrians on the street up to certain extent (Fig. 4.4.1) although the discomfort level of

    the area is quite high. In winter, PMV remains within +1.11 and -1.11, the neighbourhood remains comfortable.

    Fig. 4.4.1: Simulation results of PMV at 1.00pm the Summer day (21 June) at a height of 900mm from GL.

    Fig. 4.3.2: Simulation results of PMV at 1.00pm the winter day (22 December) at a height of 900mm from GL.

  5. Building model for indoor simulation

    The thermal behaviour of a standard apartment is simulated, which is most commonly constructed as residential unit type with the high energy use in the case study area. The following building element parameters are verified in the simulation:

    • External wall

    • Window size (WFR)

    The comfortable temperature limit for winter and summer are set at 18°C and 26°C respectively. These values are based on the minimum thermal comfort limits suggested for Guwahati. The objective of using these is to find the minimum energy consumption.

    1. Ventilation rate and internal loads of typical apartment

      In most apartments in Guwahati, Natural ventilation is achieved by opening windows. There is likely to be natural ventilation (air infiltration) even when the windows are closed. The facade construction is often masonry, which means that most air leakage paths are related to leaky windows. There are air leakage paths e.g. between the window frame and the facade. Ventilation heat losses can add up to an important part of the overall energy losses. Information on ventilation rates are required to calculate the energy use of a building.

      The typical plan of the apartment building model is used for the parametric studies. The computer model is based on a typical middle class apartment of 105 m², a living and dining hall, a kitchen, two toilets and three bedrooms (Fig. 4.5.1.1). The apartment is on the third floor and has three external walls exposed to the outdoor climate. The internal loads of the different rooms depend on how the apartment is used. The user pattern follows the typical cultural model in Guwahati, such as family size, user behaviour (opening and closing windows for ventilation) and domestic energy use. The resulting internal loads and ventilation rates are listed in Tables 4.5.1.34.5.1.5.

      Fig 4.5.1.1: Floor plan of the typical 3BHK apartment in National Games Village

      Table 4.5.1.1 Values of surface film thermal resistance for U-value calculation

      wall

      Roof

      all climatic Zones

      Composite climate, Hot-Dry climate, Warm- humid climate, and Temperate climate

      cold climate

      Rsi (m2.K/W)

      0.13

      p>0.17

      0.10

      Rse (m2.K/W)

      0.04

      0.04

      0.04

      Source: Bureau of Energy Efficiency (BEE), 2009

      External walls are studied according to their thermal performance, principally the thermal insulation. The u value of the exterior wall is calculated (Table 4.5.1.2). Since the U- value of the exterior wall is very high at 2.77 W/m2 oC, heat is easily transmitted through wall . The temperature difference between outdoor and indoor condition is very less during summer (2o-3o during summer and 3o 4o during winter).

      Sl. No

      Building Component

      Conductivity-K (W/m2 oC)

      Thickness D in M

      R=D/K (m 2

      oC/W)

      1

      Outside plastering

      0.721

      0.025

      0.035

      2

      RCC Concrete

      1.58

      0.150

      0.095

      3

      Internal plastering

      0.721

      0.015

      0.021

      4

      White Wash

      0.05

      0.002

      0.04

      5

      External surface Resistance ( 1/fo)

      0.04

      6

      Internal surface Resistance ( 1/fi)

      0.13

      TOTAL

      0.361

      U value =1/R

      2.77 W/m2 oC

      Sl. No

      Building Component

      Conductivity-K (W/m2 oC)

      Thickness D in M

      R=D/K (m 2

      oC/W)

      1

      Outside plastering

      0.721

      0.025

      0.035

      2

      RCC Concrete

      1.58

      0.150

      0.095

      3

      Internal plastering

      0.721

      0.015

      0.021

      4

      White Wash

      0.05

      0.002

      0.04

      5

      External surface Resistance ( 1/fo)

      0.04

      6

      Internal surface Resistance ( 1/fi)

      0.13

      TOTAL

      0.361

      U value =1/R

      2.77 W/m2 oC

      Table 4.5.1.2: U value Calculations of External wall

      Table 4.5.1.3 Ventilation rates and internal loads for the period 01 Oct. 31 Dec. (autumn and beginning of winter)

      Hourly Period

      Living Room

      Master Bed Room

      Bed Room

      Kitchen

      Toilet

      VR

      (ach)

      IL (W)

      VR

      (ach)

      IL (W)

      VR

      (ach)

      IL (W)

      VR

      (ach)

      IL (W)

      VR

      (ach)

      IL (W)

      01-06

      0.5

      10

      0.5

      50

      0.5

      50

      0.5

      10

      0.25

      10

      07-09

      1

      50

      1

      500

      1

      500

      1

      150

      0.25

      50

      10-14

      1.3

      100

      1.3

      100

      1.3

      100

      1.3

      300

      0.25

      50

      15-21

      1.0

      100

      1.3

      500

      1.3

      500

      1.3

      300

      0.25

      50

      22-24

      0.5

      50

      0.5

      150

      0.5

      150

      0.5

      50

      0.25

      10

      Table 4.5.1.4 Ventilation rates and internal loads for the period 01 Jan. 31 May. (Winter and Spring)

      Hourly Period

      Living Room

      Master Bed Room

      Bed Room

      Kitchen

      Toilet

      VR

      (ach)

      IL (W)

      VR

      (ach)

      IL (W)

      VR

      (ach)

      IL (W)

      VR

      (ach)

      IL (W)

      VR

      (ach)

      IL (W)

      01-06

      0.5

      10

      0.5

      50

      0.5

      50

      0.5

      10

      0.25

      10

      07-09

      0.8

      50

      3.06

      500

      3.54

      500

      2.01

      150

      0.25

      2000

      10-14

      1.3

      50

      3.06

      100

      3.54

      100

      2.01

      300

      0.25

      2000

      15-21

      1.3

      1000

      3.06

      1000

      3.54

      1000

      2.01

      300

      0.25

      50

      22-24

      0.5

      300

      0.5

      500

      0.5

      500

      0.5

      100

      0.25

      10

      Table 4.5.1.6 Ventilation rates and internal loads for the period 01 July. 31 Sept. (Summer)

      Hourly Period

      Living Room

      Master Bed Room

      Bed Room

      Kitchen

      Toilet

      VR

      (ach)

      IL (W)

      VR

      (ach)

      IL (W)

      VR

      (ach)

      IL (W)

      VR

      (ach)

      IL (W)

      VR

      (ach)

      IL (W)

      01-06

      0.5

      10

      0.5

      2000

      0.5

      2000

      0.5

      10

      0.25

      10

      07-09

      1.3

      50

      3.56

      500

      4.58

      500

      2.01

      150

      0.25

      50

      10-14

      1.3

      500

      3.56

      500

      4.58

      500

      2.01

      300

      0.25

      50

      15-21

      1.3

      500

      0.5

      2000

      0.5

      2000

      2.01

      300

      0.25

      50

      22-24

      0.5

      300

      0.5

      2000

      0.5

      2000

      0.5

      100

      0.25

      10

      Design Builder Energy plus software is used for indoor simulation of the apartment to find out the indoor temperature, hat gains, energy consumption and ventilation rate (Fig. 4.5.1.2). During summer months average indoor operative temperature remains at 29o C and outdoor dry bulb temperature remains at 31o C. While in winter months indoor operative temperature remains at 23o-24o C where as outdoor dry bulb temperature remains at 18o C.

      Fig 4.5.1.2: Indoor Temperature, Heat Gains and Energy Consumption of the typical 3BHK apartment in National Games Village throughout the year 2019 based on Design Builder energy plus simulation

    2. Results and Discussions

For determining the rate of ventilation based on wind action the wind may be assumed to come from any direction within 45° of the direction of prevailing wind. Ventilation due to external wind is given by the following formula:

Q=KAV

where

Q = Rate of air flow in m3/h;

K = Coefficient of effectiveness, which may be taken as 0.6 for wind perpendicular to openings and 0.3 for wind at an angle less than 45° to the openings;

A = Free area of inlet openings in m2; and v = Wind speed in m/h.

For Guwahati apartment the ventilation rate of different rooms are shown in the table 4.2.1 and 4.2.2

The average measured ventilation rate during the winter period is 4.68 ach ± 14%. The ventilation rates are not similar in the individual rooms (see Table 4.5.2.1). The ventilation rates are under desirable level except three bed rooms and kitchen. This average temperature difference between the inside and outside is approximately 10o C (Table

        1. indoor average + 24.2 °C and outdoor average + 14.2

          °C), the gentle wind speed (3.0 m/s), and the fact that the windows are closed most of the time (apart from morning airing). Many building codes recommend a minimum ventilation rate of 0.5 ach.

          Table 4.5.2.1 Measured ventilation rate in the tested apartment in Guwahati, 14 Dec. 07 January 2019

          Sr. No

          Room

          Room specific air

          flow rate (ach)

          WFR (%)

          Desirable Air Change rate

          Remark

          1

          Living/Dining

          0.80 ±0.05

          12.00%

          1.0

          Below desirable Level

          2

          Kitchen

          1.41 ±0.05

          10.00%

          1.5

          ok

          3

          Master Bed Room

          2.08 ±0.05

          15.0%

          0.5

          ok

          4

          Bed Room 1

          2.64 ±0.05

          25.00%

          0.5

          ok

          5

          Bed Room 2

          1.45 ±0.05

          18.00%

          0.5

          ok

          6

          Toilet 1

          0.25 ±0.05

          12.00%

          2.0

          Below desirable Level

          7

          Toilet 2

          0.30 ±0.05

          15.00%

          2.0

          Below desirable Level

          The average measured ventilation rate during the summer period is 5.93 ach ± 14%. The ventilation rates are similar in the individual rooms (see Table 4.3.2). The ventilation rates are fairly high. This is due to the fact that many windows are half opened during the day and night. The driving forces for the ventilation are fairly good. The average temperature difference between inside and outside is 5o C (indoors average + 25.4 °C and outdoors average + 30.4 °C), and the wind speed is 4.0 m/s.

          Table 4.2.2 Measured ventilation rate in the tested apartment in Guwahati, 14 July 07 August 2019

          V. CONCLUSION

          In summer, a large WFR creates a comfortable environment in daytime due to natural ventilation with average operative temperatures of 26.4°C and 26.1°C for WFR = 18% and WFR = 25% respectively. Hence present GMDA WFR of around 16.67 % is not adequate enough for a passive cooling apartment in Guwahati.

          The indoor climate in winter is considerably comfortable with the existing WFR and building elements, with an increase in temperature of 2.3°C in the daytime. However it falls below comfort level at night.

          REFERENCES

          1. ASHRAE Standard 55, 1992, Thermal environmental conditions for human occupancy, ASHRAE Inc., Atlanta.

          2. Bureau of Indian Standards (BIS). 2016. National Building Code of India 2016.

          3. Eco-Niwas Samhita 2018 (Energy Conservation Building Code for Residential Buildings) Part I: Building Envelope

          4. ENERGY CONSERVATION BUILDING CODE 2017

          5. GMDA Building Bye Laws 2014

          6. Guwahati Master Plan 2025

          7. ISO/WD7730 (2000) Ergonomics of the Thermal Environment Analytical Determination and Interpretation of Thermal Comfort Using Calculation of the PMV and PPD Indices and Local Thermal Comfort.

          8. Kubota, T., Toe, D. H. C., and Ahmad S., The effects of night ventilation technique on indoor thermal environment for residential buildings in hot-humid climate of Malaysia, Energy and Buildings 41 (2009)

          9. Mazumdar, M., 2002, Energy-efficient buildings in India, TERI, New Delhi.

          10. Milne, M. and Givoni, B., 1979, Architectural design based on climate, In Energy Conservation through Building Design, Watson,

            D. (Ed.), McGraw Hill Book Company, New York

          11. Sharma, A., Dhote, K. K., & Tiwari, R. Climatic responsive energy efficient passive technique in building, Eighteen National Convention of Architectural Engineers, Jaipur: Maulana Azad National Institute of Technology (2002) .

          12. Singh, M.K. and Mahapatra, S., 2005, Bio-climatic classification of North East India, International Seminar and Exhibition on Non- conventional and Renewable Energies, Energy Efficiency and Sustainability, Prithvi 2005, 2026 Feb., Thiruvananthapuram, India.

          13. Wayon, D.P., 1973, The role of the environment in buildings today: Thermal aspects (factors affecting the choice of a suitable room temperature), Building International.

Sr. No

Room

Room specific air

flow rate (ach)

WFR (%)

Desirable Air Change rate

Remark

1

Living/Dining

0.85 ±0.05

12.00%

1.0

Below desirable Level

2

Kitchen

1.45 ±0.05

25.00%

1.5

ok

3

Master Bed Room

2.15 ±0.05

25.00%

0.5

ok

4

Bed Room 1

2.64 ±0.05

25.00%

0.5

ok

5

Bed Room 2

1.65 ±0.05

18.00%

0.5

ok

6

Toilet 1

0.25 ±0.05

12.00%

2.0

Below desirable Level

7

Toilet 2

0.30 ±0.05

15.00%

2.0

Below desirable Level

Leave a Reply