Six Phase Transmission Line Boundary Fault Detection using Mathematical Morphology

DOI : 10.17577/IJERTV6IS120091

Download Full-Text PDF Cite this Publication

Text Only Version

Six Phase Transmission Line Boundary Fault Detection using Mathematical Morphology

Kriti Sharma and Shoyab Ali

Department of Electrical Engineering Vedant College of Engineering and Technology

Kota, India sharmakriti0012@gmail.com

Gaurav Kapoor

Department of Electrical Engineering Modi Institute of Technology

Kota, India gaurav.kapoor019@gmail.com

Abstract This paper presents a mathematical morphology based boundary protection scheme for the detection of close-in and remote-end faults that occur on six phase transmission line. A 400 kV, 50 Hz six phase transmission line of 200 km length has been simulated using MATLAB software. The proposed scheme makes use of six phase current measured at the relay location (bus-1) of a six phase transmission line. To assess the performance of the proposed method, various fault parameters are varied. Simulation results reveal the appropriateness of the proposed scheme.

Keywords Six Phase Transmission Line Protection; Mathematical Morphology; Boundary Protection; Fault Detection; Close-In And Remote-End Fault Detection.

  1. INTRODUCTION

    For the protection of six phase transmission line against the shunt and series faults, a protection scheme based on logic has been proposed by G. C. Sekhar and P. S. Subramanyam in [1]. A comparative study of electric field calculations beneath six phase and double circuit transmission lines has been described by R. M. Radwn and M. M. Samy in [2]. By the usage of charge simulation technique, calculation of electric field has been done for both double circuit and six phase transmission line at one meter above the earth level. Ebha Koley, Khushaboo Verma and Subhojit Ghosh [3] proposed hybrid WT and modular ANN based scheme for the protection of six phase transmission line which utilized the measured data of single end only. An algorithm for the over current protection of six phase transmission line with the help of numerical relay has been described by Shanker Warathe and R. N. Patel in [4] and based on test results, it was found that the numerical relay protects well six phase transmission line from over current problem. Classification of phase to phase faults on six phase transmission line by using Haar WT and ANN has been reported in [5]. F. Namdari and M. Salehi [6] proposed mathematical morphology and initial current travelling wave based high speed protection scheme for three phase transmission lines. Rapid discrimination of the fault direction and internal faults from the external faults has been done by comparing the arrival time and polarity of the initial current travelling wave captured from both the ends of a transmission

    transmission line protection scheme against lightning strikes. Paulo A. H. Cavalcante et al. [10] proposed a scheme based on simplified multi-resolution morphological gradient (SMMG) for fault location on a three phase transmission line. The proposed scheme is dependent on sampled voltage signals collected from both the ends of a transmission line. Numerous advantages of six phase power transmission line over traditional three phase power transmission lines are: six phase transmission line generates less electric field, less necessity of right of way (ROW) and tower dimensions, increased line inductance and decreased line capacitance, preserved voltage stability, and increased reactive power limit at the far end voltage point [11-14].

    In this paper, a mathematical morphology based fault identification scheme is proposed for the detection of six phase transmission line close-in and remote-end faults. At a variety of fault locations, the performance of scheme is discovered including faults at boundary locations. Distinguish explorations are done to analyze the impact of variation in fault parameters like fault type, fault location, fault resistance, ground resistance, and fault inception angle. Performance of the proposed scheme is tested from 1% of the line length up to 97.5% of the line length. Test results attained by the training of proposed technique validate the suitability of the proposed scheme under a diversity of fault circumstances.

  2. SIMULATION OF SIX PHASE TRANSMISSION LINE Test system under consideration is comprised of 400 kV,

    50 Hz, six phase transmission line of length 200 km as demonstrated in Fig.1. The six phase transmission line is connected to a load of 100 MW at the receiving end side. MATLAB software is used for the modeling and simulation of test system for numerous types of faults.

    Six Phase Transmission Line

    Generator

    Relay Load

    line under protection. Ashutosh Kumar Tiwari, Soumya Ranjan Mohanty and Ravindra Kumar Singh [7] proposed

    Bus-1

    Fault

    Bus-2

    mathematical morphology based fault detection technique for the protection of DG penetrated electrical power distribution system. Vinayesh Sulochana, Anish Fransis and Andrew Tickle [8] proposed transmission line fault detection and classification scheme based on morphology and radon processed artificial neural network. Zehui Liang et al. [9] proposed mathematical morphology and integral method based

    Fig.1. Single line diagram of six phase transmission line

  3. MATHEMATICAL MORPHOLOGY

    If f (p) is the signal [6] then its domain Df = {x0, x1,xp} and s (q) is the structuring element having domain Dq = {y1,

    y2,…yq} and p > q, where p and q are the integers, then the dilation of f(p) by s (q), denoted by (fs) can be defined as: –

    yd (p) = (fs)(p)=max{f(p-q)+s(q),0(p-q)p,q0}. (1)

    The erosion of f (p) by s (q) denoted as (fs) can be defined as: –

    ye (p) = (fs)(p)=min{f(p+q)-s(q), 0(p+q)p,q0}. (2)

  4. PROPOSED FAULT DETECTION SCHEME Fig. 2 depicts proposed fault detection scheme [20].

    Six phase current

    Calculate dilate and erode of six phase current

    Calculate Gradient-1 [Dilate-Erode]

    No fault

    And its Kurtosis (K1) of six phase current

    No fault

    Calculate Gradient-2 [Signal-Erode]

    And its Kurtosis (K2) of six phase current

    No No

    5.1 Phase-AD-g close-in fault

    The proposed scheme is examined for close-in relay phase- AD-g fault occurring at 1% from the relay location with fault inception time of 0.0133 seconds having R f = 10, R g = 15. The six phase current for the period of phase-AD-g fault is shown in Fig. 3. The process of fault detection using mathematical morphological filter during phase- AD-g fault occurring at 1% from bus-1 at FIT = 0.0133 seconds with R f = 10 and R g = 15 can be seen from Fig. 4 to Fig. 5. Fig. 4 to Fig. 5 clarifies the magnitude of gradient-1, 2 and 3 of phase- A and D for the duration of phase-AD-g fault and from Fig. 4 and 5 it is clearly observed that the magnitude of gradients- 1, 2 and 3 of phase-A and D during phase-AD-g fault is higher than the magnitude of gradients-1, 2 and 3 of other phases. Table I summarizes the response of the proposed scheme for phase-AD-g fault occurring at 1% from relay location. As viewed from Table I, the magnitude of gradient-1, 2 and 3 of faulted phase (Phase-A and D) is more than the magnitude of gradient 1, 2 and 3 of un-faulted phase and this explains that the proposed mathematical morphological based fault detector in actual fact detects phase-AD-g fault occurred at 1% from the relay location.

    x 10

    Fault detected

    Fault detected

    Yes Is

    rad-2|faulted phase

    |Grad-2| un-faulted

    Is Yes

    4

    current(:,1)

    current(,2)

    current(:,3)

    current(:,4)

    current(:,5)

    current(:,6)

    1.5

    1

    AD-g

    |Grad-1|faulted phase

    rad-1| un-faultedphase

    > |G

    |G

    Calculate Gradient-3 [Dilate-Signal]

    And its Kurtosis (K3) of six phase current

    >

    phase

    No fault

    Is No

    0.5

    Current (A)

    0

    -0.5

    -1

    -1.5

    0 0.5 1 1.5 2 2.5 3

    |Grad-3|faulted phase >

    Samples

    5

    x 10

    |Grad-3| un-faulted phase

    Fault detected

    Yes

    Fig. 3. Six phase current during phase-AD-g fault at 1% from bus-1 at FIT = 0.0133 seconds with R f = 10 and R g = 15

    Fig. 2. Proposed fault detection scheme

    Gradient-1 (grad1), gradient-2 (grad2) and gradient-3 (grad3) are the three types of mathematical morphological filter coefficients [10]. Following the calculation of these three coefficients, trip decision has been taken. Following six phase fault current decomposition using mathematical morphology filter, if magnitude of gradient-1, 2 or 3 of the faulted phase is

    Grad1

    12000

    10000

    Magnitude

    8000

    6000

    4000

    2000

    0

    0 1 2 3

    Grad2

    8000

    7000

    6000

    Magnitude

    5000

    4000

    3000

    2000

    1000

    0

    0 1 2 3

    Grad3

    8000

    7000

    6000

    Magnitude

    5000

    4000

    3000

    2000

    1000

    0

    0 1 2 3

    found larger than the magnitude of gradient-1, 2 or 3 of a healthy phase, the relay detects the fault and issue trip

    Samples

    4

    x 10

    Samples

    4

    x 10

    Samples

    4

    x 10

    command for the tripping of faulty phase (s). For numerous types of faults, the proposed scheme is tested with various

    Fig. 4. Gradients-1, 2, 3 of phase-A during phase-AD-g fault

    fault parameters variation.

  5. TEST RESULTS AND DISCUSSIONS

    To scrutinize the performance of mathematical morphological based fault detector, the proposed scheme is tested for various fault cases with variation in fault type, fault location, fault resistance, ground resistance and fault inception time.

    Grad1

    8000

    7000

    6000

    Magnitude

    5000

    4000

    3000

    2000

    1000

    Grad2

    7000

    6000

    5000

    Magnitude

    4000

    3000

    2000

    1000

    Grad3

    7000

    6000

    5000

    Magnitude

    4000

    3000

    2000

    1000

    0

    0 1 2 3

    0

    0 1 2 3

    0

    0 1 2 3

    Samples

    4

    x 10

    Samples

    4

    x 10

    Samples

    4

    x 10

    Fig. 5. Gradients-1, 2, 3 of phase-D during phase-AD-g fault

    TABLE I. RELAY OUTPUT FOR PHASE-AD-G FAULT AT 1% FROM BUS-1 AT

    FIT = 0.0133 SECONDS WITH R F = 10 AND R G = 15

    Phase

    Outputs A B C D E F

    10000

    8000

    Magnitude

    6000

    4000

    2000

    Grad1

    6000

    5000

    Magnitude

    4000

    3000

    2000

    1000

    Grad2

    6000

    5000

    Magnitude

    4000

    3000

    2000

    1000

    Grad3

    Dil

    1.2722*

    929.2

    1.0302*

    1.2759*

    865.2

    1.1426*

    0

    0 2000 4000 6000 8000 10000

    Samples

    0

    0 2000 4000 6000 8000 10000

    Samples

    0

    0 2000 4000 6000 8000 10000

    Samples

    Fig. 7. Gradients-1, 2, 3 of phase-A during phase-ABEF-g fault

    8000

    7000

    6000

    Magnitude

    5000

    4000

    3000

    2000

    1000

    Grad1

    5000

    4000

    Magnitude

    3000

    2000

    1000

    Grad2

    5000

    4000

    Magnitude

    3000

    2000

    1000

    Grad3

    0

    0 2000 4000 6000 8000 10000

    Samples

    0

    0 2000 4000 6000 8000 10000

    Samples

    0

    0 2000 4000 6000 8000 10000

    Samples

    Fig. 8. Gradients-1, 2, 3 of phase-B during phase-ABEF-g fault

    10^4

    827

    10^3

    10^4

    665

    10^3

    Erd 1.2712*

    853.9

    960.7

    1.2732*

    767.0

    1.0743*

    10^4

    529

    028

    10^4

    688

    10^3

    Grad1 1.1307*

    1.5519*

    1.4875*

    7.7755*

    1.4875*

    1.3429*

    10^4

    10^3

    10^3

    10^3

    10^3

    10^3

    7.8811*

    1.2593*

    1.4458*

    6.3013*

    1.4448*

    1.0005*

    Grad2 10^3

    10^3

    10^3

    10^3

    10^3

    10^3

    Grad3 7.8811*

    1.2593*

    1.4458*

    6.3013*

    1.4448*

    1.0005*

    10^3

    10^3

    10^3

    10^3

    10^3

    10^3

      1. Phase-ABEF-g remote-end fault

        The proposed scheme is tested for remote-end phase- ABEF-g low resistance fault occurring at 95% from the relay location with fault inception time of 0.02833 seconds having R f = 0.5, R g = 1. The six phase current for the duration of phase-ABEF-g fault is shown in Fig. 6. The process of fault detection using mathematical morphological filter during phase- ABEF-g fault occurring at 95% from bus-1 at FIT =

        10000

        8000

        Magnitude

        6000

        4000

        2000

        0

        Grad1

        0 2000 4000 6000 8000 10000

        Samples

        7000

        6000

        5000

        Magnitude

        4000

        3000

        2000

        1000

        0

        Grad2

        0 2000 4000 6000 8000 10000

        Samples

        7000

        6000

        5000

        Magnitude

        4000

        3000

        2000

        1000

        0

        Grad3

        0 2000 4000 6000 8000 10000

        Samples

        0.02833 seconds with R f = 0.5 and R g = 1 can be seen from Fig. 7 to Fig. 10. Fig. 7 to Fig. 10 describes the

        Fig. 9. Gradients-1, 2, 3 of phase-E during phase-ABEF-g fault

        magnitude of gradient-1, 2 and 3 of six phases for the duration of phase-ABEF-g fault and from Fig. 7 to Fig. 10 it is clearly observed that the magnitude of gradients-1, 2 and 3 of phase- A, B, E and F during phase-ABEF-g fault is higher than the magnitude of gradients-1, 2 and 3 of other phases. Table II highlights the response of the proposed scheme for phase- ABEF-g fault occurring at 95% from relay location. As viewed from Table II, the magnitude of gradient-1, 2 and 3 of faulted phase is higher than the magnitude of gradient 1, 2 and

        Grad1

        9000

        8000

        7000

        Magnitude

        6000

        5000

        4000

        3000

        2000

        1000

        0

        0 2000 4000 6000 8000 10000

        Samples

        Grad2

        6000

        5000

        Magnitude

        4000

        3000

        2000

        1000

        0

        0 2000 4000 6000 8000 10000

        Samples

        Grad3

        6000

        5000

        Magnitude

        4000

        3000

        2000

        1000

        0

        0 2000 40006000 8000 10000

        Samples

        3 of un-faulted phase and this explains that the proposed mathematical morphological based fault detector in point of fact detects phase-ABEF-g fault occurred at 95% from the relay location which is mainly a remote-end low resistance fault.

        Fig. 10. Gradients-1, 2, 3 of phase-F during phase-ABEF-g fault

        TABLE II. RELAY OUTPUT FOR PHASE-ABEF-G FAULT AT 95% FROM BUS-1

        Phase

        Outputs A

        B

        C

        D

        E

        F

        Dil 3.1552*

        7.8973*

        1.5010*

        1.2483*

        4.5779*

        6.6614*

        10^3

        10^3

        10^3

        10^3

        10^3

        10^3

        Erd 3.0995*

        7.7891*

        969.8

        966.1

        4.3562*

        5.9316*

        10^3

        10^3

        007

        331

        10^3

        10^3

        Grad1 9.5591*

        7.7628*

        2.3589*

        1.9644*

        9.7774*

        8.4613*

        10^3

        10^3

        10^3

        10^3

        10^3

        10^3

        Grad2 5.5240*

        4.7516*

        1.8681*

        1.3764*

        6.5126*

        5.7584*

        10^3

        10^3

        10^3

        10^3

        10^3

        10^3

        Grad3 5.5240*

        4.7516*

        1.8681*

        1.3764*

        6.5126*

        5.7584*

        10^3

        10^3

        10^3

        10^3

        10^3

        10^3

        AT FIT = 0.02833 SECONDS WITH R F = 0.5 AND R G = 1

        8000

        6000

        4000

        Current (A)

        2000

        0

        -2000

        -4000

        -6000

        ABEF-g

        current(:,1)

        current(:,2)

        current(:,3)

        current(:,4)

        current(:,5)

        current(:,6)

        -8000

        -10000

        0 0.5 1 1.5 2 2.5 3

        Samples

        4

        x 10

        Fig. 6. Six phase current during phase ABEF-g fault at 95% from bus-1 at FIT = 0.02833 seconds with R f = 0.5 and R g = 1

      2. Phase-ABCDEF-g remote-end fault

    The proposed scheme is examined for remote-end phase- ABCDEF-g low resistance fault occurring at 85% from the relay location with fault inception time of 0.03166 seconds having R f = 10, R g = 15. The six phase current for the period of phase-ABCDEF-g fault is shown in Fig. 11. The procedure of fault detection using mathematical morphological filter for the period of phase- ABCDEF-g fault happening at

    85% from bus-1 at FIT = 0.03166 seconds with R f = 10 and

    Grad1

    14000

    12000

    10000

    Magnitude

    Magnitude

    8000

    6000

    4000

    2000

    0

    0 500 1000 1500 2000 2500

    Samples

    Grad2

    14000

    12000

    10000

    Magnitude

    8000

    6000

    4000

    2000

    0

    0 500 1000 1500 2000 2500

    Samples

    Grad3

    14000

    12000

    10000

    8000

    6000

    4000

    2000

    0

    0 500 1000 1500 2000 2500

    Samples

    R g = 15 can be seen from Fig. 12 to Fig. 17. Fig. 12 to Fig.

    Fig. 14. Gradients-1, 2, 3 of phase-C during phase-ABCDEF-g fault

    17 illustrates the magnitude of gradient-1, 2 and 3 of six phases for the period of phase-ABCDEF-g fault and from Fig. 12 to Fig. 17 it is noticeably observed that the magnitude of gradients-1, 2 and 3 of all six phases during phase- ABCDEF-g fault increases. Table III summarizes the response of the proposed scheme for phase-ABCDEF-g fault occurring at 85% from relay location. As inspected from Table

    12000

    10000

    Magnitude

    8000

    6000

    4000

    2000

    Grad1

    12000

    10000

    Magnitude

    8000

    6000

    4000

    2000

    Grad2

    12000

    10000

    Magnitude

    8000

    6000

    4000

    2000

    Grad3

    III, the magnitude of gradient-1, 2 and 3 of all six faulted phase raises and this clarifies that the proposed mathematical

    0

    0 500 1000 1500 2000 2500

    Samples

    0

    0 500 1000 1500 2000 2500

    Samples

    0

    0 500 1000 1500 2000 2500

    Samples

    morphological based fault detector in point of fact detects

    Fig. 15. Gradients-1, 2, 3 of phase-D during phase-ABCDEF-g fault

    phase-ABCDEF-g fault occurred at 85% from the relay location which is essentially a remote-end low resistance fault.

    14000

    12000

    Grad1

    14000

    12000

    Grad2

    14000

    12000

    Grad3

    4

    x 10

    current(:,1)

    current(:,2)

    current(:,3)

    current(:,4)

    current(:,5)

    current(:,6)

    1

    ABCDEF-g

    10000

    Magnitude

    8000

    10000

    Magnitude

    8000

    10000

    Magnitude

    8000

    0.5

    6000

    4000

    6000

    4000

    6000

    4000

    Current (A)

    2000

    0

    0

    0 500 1000 1500 2000 2500

    Samples

    2000

    0

    0 500 1000 1500 2000 2500

    Samples

    2000

    0

    0 500 1000 1500 2000 2500

    Samples

    -0.5

    Fig. 16. Gradients-1, 2, 3 of phase-E during phase-ABCDEF-g fault

    -1

    0 0.5 1 1.5 2 2.5 3

    14000

    Grad1

    14000

    Grad2

    14000

    Grad3

    Samples

    4

    x 10

    12000

    12000

    12000

    Fig. 11. Six phase current during phase ABCDEF-g fault at 85% from bus-1 at FIT = 0.03166 seconds with R f = 10 and R g = 15

    10000

    Magnitude

    8000

    10000

    Magnitude

    8000

    10000

    Magnitude

    8000

    14000

    12000

    10000

    Magnitude

    8000

    Grad1

    14000

    12000

    10000

    nitude

    8000

    Grad2

    14000

    12000

    10000

    nitude

    8000

    Grad3

    6000

    4000

    2000

    0

    0 500 1000 1500 2000 2500

    Samples

    6000

    4000

    2000

    0

    0 500 1000 1500 2000 2500

    Samples

    6000

    4000

    2000

    0

    0 500 1000 1500 2000 2500

    Samples

    6000

    6000

    Mag

    6000

    Mag

    4000

    4000

    4000

    2000

    0

    2000

    0

    2000

    0/p>

    TABLE III. RELAY OUTPUT FOR PHASE-ABCDEF-G FAULT AT 85% FROM

    BUS-1 AT FIT = 0.03166 SECONDS WITH R F = 10 AND R G = 15

    Fig. 17. Gradients-1, 2, 3 of phase-F during phase-ABCDEF-g fault

    0 500 1000 1500 2000 2500

    Samples

    0 500 1000 1500 2000 2500

    Samples

    0 500 1000 1500 2000 2500

    Samples

    Phase

    Outputs A

    B

    C

    D

    E

    F

    5.4351*

    5.7897*

    8.1342*

    6.0585*

    5.4672*

    8.3995*

    Dil 10^3

    10^3

    10^3

    10^3

    10^3

    10^3

    5.0707*

    5.3053*

    7.5893*

    5.4177*

    5.0268*

    7.9739*

    Erd 10^3

    10^3

    10^3

    10^3

    10^3

    10^3

    Grad1 1.2881*

    1.1848*

    1.2776*

    1.1848*

    1.2776*

    1.2881*

    10^4

    10^4

    10^4

    10^4

    10^4

    10^4

    Grad2 1.2881*

    1.1743*

    1.2776*

    1.1743*

    1.2776*

    1.2881*

    10^4

    10^4

    10^4

    10^4

    10^4

    10^4

    Grad3 1.2881*

    1.1743*

    1.2776*

    1.1743*

    1.2776*

    1.2881*

    10^4

    10^4

    10^4

    10^4

    10^4

    10^4

    Fig. 12. Gradients-1, 2, 3 of phase-A during phase-ABCDEF-g fault

    12000

    10000

    Magnitude

    8000

    6000

    4000

    Grad1

    12000

    10000

    Magnitude

    8000

    6000

    4000

    Grad2

    12000

    10000

    Magnitude

    8000

    6000

    4000

    Grad3

    2000

    0

    0 500 1000 1500 2000 2500

    Samples

    2000

    0

    0 500 1000 1500 2000 2500

    Samples

    2000

    0

    0 500 1000 1500 2000 2500

    Samples

    Fig. 13. Gradients-1, 2, 3 of phase-B during phase-ABCDEF-g fault

  6. CONCLUSION

In this paper, a mathematical morphology based boundary protection scheme is proposed for six phase transmission line. The proposed scheme exploits dilation and erosion coefficients of six phase fault current measured at the relay location (Bus- 1). The proposed scheme effectively detects both close-in and remote-end faults that occur on six phase transmission line. The proposed scheme is tested for numerous categories of boundary faults with fault parameters variation. Simulation results show that both close-in and remote-end faults are correctly detected by mathematical morphology based fault detection scheme.

REFERENCES

  1. G. C. Sekhar and P. S. Subramanyam, A Logic Based Protection Scheme for Six Phase Transmission System against Shunt and Series Faults, WJMS, vol.-12, no.-2, pp. 125-136, March 2016.

  2. R. M. Radwn and M. M. Samy, Calculation of Electric Fields Underneath Six Phase Transmission Lines, JES, vol.-12, no.-4, pp. 839- 851, October 2016.

  3. Ebha Koley, Khushaboo Verma and Subhojit Ghosh, An Improved Fault Detection, Classification and Location Scheme Based on Wavelet Transform and Artificial Neural Network for Six Phase Transmission Line using Single end Data Only, Springer Plus, pp. 1-22, September 2015.

  4. Shanker Warathe and R. N. Patel, Six Phase Transmission Line Over Current Protection by Numerical Relay, ICACCS-IEEE, Janurary 2015.

  5. Ravi Kumar, Ebha Koley, Anamika Yadav and A.S. Thoke, Fault Classification of Phase to Phase Fault in Six Phase Transmission Line using HAAR Wavelet and ANN, IEEE-SPIN, pp. 5-8, March 2014.

  6. F. Namdari and M. Salehi, A High-Speed Protection Scheme Based on Initial Current Travelling Wave for Tranamission Lines Employing Mathematical Morphlogy, IEEE Transactions on Power Delivery, vol.- 32, no.-1, pp. 1-8, February 2017.

  7. Ashutosh Kumar Tiwari, Soumya Ranjan Mohanty and Ravindra Kumar Singh, A Novel Fault Detection Technique in Distribution System with the Penetration of DG using Mathematical Morphology, IJST, vol.-9, no.-44, pp. 1-5, November 2016.

  8. Vinayesh Sulochana, Anish Fransis and Andrew Tickle, Morphology Based Radon Processed Neural network for Transmission Line Fault Detection, IEEE-ICACCI, pp. 1137-1143, August 2015.

  9. Zehui Liang, Yongli Zhu, Lili Dai and Qingfeng Wen, Identification of Lightining Strikes on Transmission Lines Based on Mathematical Morphology and Integral Method, IEEE-IET-RPGC, September 2013.

  10. Paulo A. H. Cavalcante et al., A Transmission Line Two-end Fault Location Approach Based on Mathematical Morphology, IEEE- PESGM, July 2013.

  11. M. A. Golkar, Reza Shariatinasab and Mohsen Akbari, Voltage Stability Analysis in Conversion of Double Three Phase to Six Phase Transmission Line, IEEE Int. Conf. on P and E, pp. 172-177, January 2011.

  12. Siti Amely and Mohd. Wazir Bin Mustafa, Analysis of Six Phase System for Transmission Line, Int. Conf. on PEOCO, pp. 111-118, June 2008.

  13. Zakir Husain, R. K. Singh and S. N. Tiwari, Multi Phase Power Transmission Systems with TCSC, Int. Conf. on AEE, pp. 246-250, May 2007.

  14. Zakir Husain, R. K. Singh and S. N. Tiwari, Multi Phase Transmission Line: Performance Characteristics, IJMCS, vol.-1, no.-2, May 2007.

  15. A. A. Hajjar and M. M. Mansour, Fault Location for Six Phase Transmission Lines Based in the Wavelet Transform of the Fault Induced High Frequency Transients, Int. Conf. on UPE, pp. 252-256, March 2008.

  16. M. W. Mustafa, M. R. Ahmad and H. Shareef, Fault Analysis on Double Three Phase to Six Phase Converted Transmission Line, Int. Conf. on Power Engineering, pp. 1-5, May 2006.

  17. M. W. Mustafa and M. R. Ahmad, Transient Stability Analysis of Power System with Six Phase Converted Transmission Line, IEEE Int. Conf. on Power and Energy, pp. 262-266, April 2007.

  18. R. Billinton, S.O. Faried and M. Fotuhi, Composite System Reliability Evaluation Incorporating a Six Phase Transmission Line, IEE Proc. G, T and D, vol.-150, no.-4, pp. 413-419, July 2003.

  19. A. A. Hajjar, M. M. Mansour, H. E. A Tallat and S. O. Faried, Distance Protection for Six Phase Transmission Lines Based on Fault Induced High Frequency Transients and Wavelets, IEEE-CCECE, pp. 7-11, August 2002.

  20. D. J. Zhang , Q. Li, J. F. Zhang, Q. H. Wu and D. R. Turner, Improving the Accuracy of Single-ended Transient Fault Locators Using Mathematical Morphology, IEEE-ICPST-PowerCon, pp. 788-792, October 2002.

Leave a Reply