Simulation Study of Voltage Surge Distribution in a Transformer Winding

DOI : 10.17577/IJERTV5IS010332

Download Full-Text PDF Cite this Publication

Text Only Version

Simulation Study of Voltage Surge Distribution in a Transformer Winding

R.V Srinivasamurthy [1] Pradipkumar Dixit [2]

Research Scholar, Jain university Professor, EEE Dept

Prof and Head, EEE Dept M.S. Ramaiah Institute of Technology EWIT, Bangalore. Bangalore.

Abstract: In this paper simulation study of voltage surge distribution in a transformer winding using P-Spice Orcad is presented. A model based on ladder network for representing HV side of the transformer winding is used.The surge behavior of the transformer winding is studied for lightning and VFTO surge voltages. The study is carried out for continuous disc type winding and interleaved winding for the cases of without skin effect, with skin effect and mutual coupling.

Keywords: Disc winding, Interleaved winding, Modeling, Surge performance, Transformer.

  1. INTRODUCTION

    Power transformers play a very important role in power system. Transformers operating in power grid or in industrial environment are subjected to lightning, switching and very fast transient overvoltages (VFTO) phenomenon. Surge voltages whether they be system generated or those that occur due to natural phenomenon have detrimental effects on transformer windings unless protective measures are put in place. Detailed knowledge of surge voltage distribution along the transformer winding helps in the design of appropriate winding structure and insulation co- ordination for transformers[1]. Switching operations in a gas insulated substation (GIS) and lightning impulses are known to produce VFTOs which are dangerous for the transformer and motor insulation. Also in medium voltage systems where vacuum circuit breakers are used reignition causes high-frequency oscillations which can be dangerous because of their short rise time. Under special circumstances the terminal overvoltages can arise close to the transformer basic impulse level (BIL). These overvoltages are characterized by a very short rise time. The experience shows that VFTOs within GIS can be expected to have even a rise time of 0.1 µs and an amplitude of about 2.5 p.u. The inter-turn insulation is particularly vulnerable to high-frequency oscillation and therefore the study of the distribution of inter turn over- voltages is of essential interest [2]. As a first step in this direction distribution of over voltages for inter sections is presented in this paper.

  2. PROBLEM DEFINITION

    The present paper discuses the study of voltage distribution of a power transformer winding when it is subjected to lightning and VFTO surges. The studies have been made on an electromagnetic analogue model of one HV winding limb of a 11kV/33kV, 3MVA DYn 50Hz power transformer. Surge analysis is carried out for continous disc winding and interleaved winding for the cases of without skin effect, with skin effect and with mutual coupling effect, assuming that the response of a well constructed model is farely in good agreement with that of the original. For this purpose the HV winding of the transformer and the different generators are modeled in P- Spice [3].

  3. P-SPICE MODEL FOR SURGE ANALYSIS

    Fast and very fast front transient in transformers are commonly analyzed using internal models, which can take into account the distribution of the incident surge along the windings. These models are described either by distributed parameters using the transmission line theory or as a ladder connection of lumped parameter segments. The latter model is used wherein the transformer as been modeled by a network of distributed parameters of individual turns [4].

    1. Transformer Parameters: The transformer model used for the purpose of study is a 11/33 kV, 3MVA DYn continuous disk type whose details are as follows [3].

      • Outer diameter of each 33kV winding=0.524m

      • Inner diameter of each 33kV winding=0.424m

      • Axial length of each 33kV and 11kV winding=0.77m

      • Number of discs in each 33kV winding=80

      • Axial length of each 33kV and 11kV disc= 0.0066m

      • Average number of turns/ 33 kV disc= 19

      • Outer diameter of each 11kV winding=0.38m

      • Axial length of bare conductor for each 33 kV disc= 0.006m

      • Gap between two adjacent discs of each 33kV winding= 0.00288m

      • Diameter of tank axially halved= 0.595m

      • Inner diameter of the 10th turn = 0.4714m

    2. Winding details used in the present study

    For the purpose of simulation continuous disc winding and interleaved winding are considered.

    a) Continuous disc winding :

    1. Self-inductance Li of the disc coil

      The self inductance of the 33kV disc coil is calculated from the following equation [6]

      Lo=4 10-7 RN2{ln (SR/R ) 2} H (1)

      The continuous disc windings are primarily used, 1 1

      in high capacity transformers. These coils are initially Wound in the ordinary manner, beginning from the cylinder and outward, and then these coils are transposed in the reverse order The conductors are slackened somewhat in order to Make the reversing easier and the conductor running from the drum is again tensioned. This facilitates the continuous inter connection of coils without any soldered joints. A typical continuous

    2. Capacitance to earth (Cg)

      A delta connected transformer winding with its side limb winding impulsed, will have two components of Cg.

      1. Capacitance between impulsed HV winding and earthned LV winding (C1) which can be calculated using co-axial cylinder formula.

        disc winding is shown in Fig. 1

        27r

        a

        a

        c =

        c =

        1 lnb

        F (2)

      2. Capacitance between impulse side limb HV winding and transformer tank (C2), which can be calculated by considering the tank as a co-axially halved cylinder

      Fig. 1. Continuous Disc Winding

      c2 = 7r

      lnb

      lnb

      a

      F (3)

      b) Interleaved Winding :

      The inherent disadvantage of low series capacitance of the continuous disc winding was over come by electro static shielding till the advent of the interleaved winding. The original interleaved winding was introduced and patented by G F. Stearn in 1950. A simple disposition of turns in some particular ways increases the series capacitance of the interleaved winding to such an extent that a near uniform initial voltage distribution can be obtained. A typical interleaved winding is shown in Fig 2[5].

      The total ground capacitance for disc is,

      Cg=C1+C2. F (4)

    3. Series capacitance(Csi)

      Series capacitance of a disc coil has two components

      1. Inter-turn capacitance(Ct)

        This capacitance is calculated using the expression for the capacitance between two axial cylindrical electrodes

        2

        lnb

        lnb

        Ct= F (5)

        a

        Fig 2. Interleaved Winding

        c) Parameter Calculations for Disc & Interleaved winding:

        Winding parameters and their calculation for the transformer considered are discussed below.

        b) Inter-disc capacitance(Cd)

        For calculating Cd the adjacent discs are considered as two parallel plate electrodes.

        A

        Cd= d F (6)

        The total series capacitance of a disc

        Cs=(Ct/N1)+(4/3 Cd) F (7)

        Where, N1= No of turns per disc.

        The calculated values of Self inductance of disc coil (Li), Capacitance to earth (Cg) & Series capacitance are shown in Table1

        Table1: Parameters of hv winding

        C1=0.01µF C2=1nF R1=400 R2=7k

        Parameters

        Interleaved winding

        Self inductance of disc coil

        1.294x 10-3H/Section

        1.294x 10-3H/section

        Capacitance to earth

        66.28 pF /section

        66.28 pF /section

        Series capacitance

        233.65pF/section

        700.96pF/section

        Parameters

        Continues Disc winding

        Interleaved winding

        Self inductance of disc coil

        1.294x 10-3H/Section

        1.294x 10-3H/section

        Capacitance to earth

        66.28 pF /section

        66.28 pF /section

        Series capacitance

        233.65pF/section

        700.96pF/section

    4. Calculation of Mutual Inductance

    Maxwell obtained an expression for the Mutual inductance between two Co-axial circle in the form of converging series which is often more convenient to use than the eleptical integral formula and when the circles are nearly of the same radii and relatively near each other, the value given is generally sufficiently exact [6].

    Lg1=1nH

    Fig.4. Lightning impulse generator

    The simulated waveform of the output of the generator is shown in Fig 5.

    8a 3d2

    M0= 4na[log d (1 + 16a2 )] Neglecting higher order terms (8)

    a=Radius of the coil d=Distance between the coils

    823.54

    3 .2882

    M0=4n 23.54[log( 1.288 ){1 + 1623.542}]

    (9)

    =832.86cms

    M12=n2 M = 192 832.86 = 0.3m (10)

    Similarly mutual inductance values for other sections are calculated.

    The completed model of one limb of HV winding for PSPICE simulation is shown in Fig.3

    Fig.3. Simulated model of HV winding.

    1. Modeling of lightning impulse generator

      The circuit diagram of lightning impulse generator with the calculated values of parameters is as shown in Fig 4.

      Fig.5. Output voltage of the Lightning generator

      From the output waveform it is found that the value of front time of 1µs and fall time of 50µs which is in agreement with the standard specification 1.2/50µs±30%/±20%.

    2. Modeling of VFTO generator

      C1=0.01µF C2=1000pF R2=70 R1=40 Lg1=0.048mH Lg2=0.047mH

      Fig.6. VFTO Generator

      The circuit diagram of VFTO generator with the calculated values of the parameters is shown in Fig 6.

      The simulated waveform of the output of the VFTO generator is shown in Fig 7.

      Fig.7. Output voltage of the VFTO generator

      From the output waveform the measured time period is 1.67µs and hence the frequency is 598kHz which is in agreement with [7].

    3. Skin effect calculations

      The resistance of the winding taking skin effect into consideration is calculated for both lightning and VFTO inputs which is shown in table 2.

      Table2: Resistance values

      Type of surge voltage

      Resistance values with skin effect

      Lightning impulse

      0.0325

      VFTO

      0.0487

  4. RESULTS AND DISCUSSIONS

    The simulation of the model is carried out by connecting the HV winding to the VFTO generator. The voltage at different nodes in disc type winding for VFTO input is shown in Fig 8.

    Fig.8 Voltage Distribution in Disc type winding for VFTO input.

    Fig.9. Voltage surge distribution in interleaved winding for VFTO input

    Fig 8 and 9 shows voltage distribution at different nodes due to VFTO input on a Disc type winding and interleaved winding. From the graphs it is observed that the voltage distribution is almost uniform when skin effect is taken into consideration.

    The simulation of the model is carried out by connecting the HV winding to the Lightning impulse generator. The voltages measured at various nodes for the cases of without, with Skin effect and mutual coupling effect are shown in Fig 10 and 11.

    Fig.10. Voltage Distribution in disc type winding for Lightning input

    Fig.11. Voltage Distribution in inter leaved winding for Lightning input

    Fig.10 and 11 shows voltage distribution at different nodes due to lightning impulse input on a Disc type and interleaved type winding. Here also it is evident that voltage distribution is almost uniform when skin effect taken into consideration.

  5. CONCLUSIONS

In the present paper extensive observation study on voltage distribution have been made on surge model of a 3MVA,33/11kV,3phase,50Hz,DYn Transformer. The studies cover voltage distribution in the winding when it is subjected to VFTO and Lightning impulse surges. These studies are carried out for the cases of without skin effect, with skin effect and with mutual coupling. For design engineer it is very important to analyse the effect of transients on the voltage distributions of power transformers to develop reliable insulation designs at low cost [8].

    • The results have led us to the conclusion that the voltage peak occurs at the initials sections than at the end

    • Time taken to reach peak values at different

sections is different when the modules of the transformers are studied for the cases of without skin effect and with skin effect.

  • Almost uniform distribution of voltage is observed when skin effect is taken into account.

A possible direction for extension of this research is to analyse the model for switching impulse and also taking end shield into consideration.

REFERENCES

  1. A Study of the initial surge distribution in concentric transformer windings G.M Steven IEEE Winter power meeting Sep 1964.

  2. Merjan Popov, Lou Vander sluis, G.C Papp, computation of very fast transient over voltages in transformer windings, IEEE transactions on power delivery Vol 18, no 4,.Pages 1268-1274

    ,October 2003.

  3. Computer aided analysis of surge performance of transformer winding with one end earthed, S.Munshi, C.K.Roy, J.R.Biswas, Journal of Institution of Engineers, Electrical Engineering Division, Vol 70, Issue:01, Pages 9-23, 1989.

  4. Pablo Gomez, Francisco de Leon, Impulse- response analysis of Torroidal core distribution transformer for dielectric design IEEE transaction power delivery Vol 26, No 2, pages 1231-1238, April 2011.

  5. S.V.Kulakarni, S.A.Khaparde, Transformer Engineering Marcel Dekker Inc., Network, 2005.

  6. F.W. Grover, Inductance Calculations Working Formulas and Tables, Dover Publications, New York.

  7. Analysis of fast transient voltage distribution in Transformer windings under different insulation conditions, Mark Florkowisky,Jakus Furgal and Piotr Pajak,IEEE transactions on Dielectrics&electric insulation,vol19,no6, pages 1991- 1998,Deceber2012

  8. Non linear voltage distribution in windings of power transformer, Ms Kaveri Bhuyan, Dr. Saibal Chaterjee, International Jornal of Engineering Research and Technology,Vol1,Issue 4,June 2012.

ACKNOWLEDGEMENT

The authors wishes to acknowledge the support given by the management of East West Institute of Technology, M.S Ramaiah Institute of Technology and Jain University.