Seismic Analysis of Supplemental Cable Damping System in Transmission Masts

DOI : 10.17577/IJERTV7IS050097

Download Full-Text PDF Cite this Publication

Text Only Version

Seismic Analysis of Supplemental Cable Damping System in Transmission Masts

Neethi B.

Assistant Professor

Civil Engineering Department, College of Engineering Muttathara, Trivandrum, Kerala, India

AbstractVast destruction and devastation during the recent earthquakes have exposed the serious deficiencies in the prevalent design and construction practices and have created new awareness about the disaster preparedness and mitigation methods. This paper presents the application of damage avoidance design philos- ophy to a steel mast, to develop an appropriate mechanism to mit- igate the effects of an earthquake by using supplemental cable damping system with fuse-bars parallel to the dampers. Rigorous studies are conducted on the structure to develop a supplemental damping mechanism. The control system consists of supplemental dampers acting through a cable connected to the structure on the sides of the steel structure. The cable layout is determined itera- tively based on the first mode characteristics to counteract the inertial forces in the structure, in a way to reduce the overturning moments.The concept development and design are carried out using capacity-demand spectrum method and is verified by non- linear time history analysis using SAP 2000. Seismic performance and response evaluation suggests that a well designed supple- mental cable damping system with fuse-bars can significantly re- duce the vulnerability to damaging effects during an earthquake.

Keywords Capacity Demand Spectrum, Damage avoidance Design, Fuse, Mast, Pushover Analysis, Supplemental Cable Damping

  1. INTRODUCTION

    The current earthquake resistant design objectives are mainly achieved by enhancing ductility and structural strength- ening so that it withstands the earthquake with some damage or severe damage, but without collapse. This implies that the damage should be controlled to acceptable levels and at rea- sonable costs. But this ductile design philosophy suffers from the inability to avoid damage during strong earthquakes. Even if the damages are moderate, the structure may be required to be taken out of service while inspection and repairs are under- taken. In order to meet these challenges, recent advances in Seismic Engineering have focused on an alternative design methodology; Damage Avoidance Design (DAD) philosophy, introduced by Mander and Cheng [3], where a structure is de- signed to withstand a major seismic event with minimal or re- pairable damages. This typically involves incorporating mech- anisms in the structure that can control loads and sustain large deformations without causing damage.

    Elsa Joby Structural Engineer

    Spacecase Architects and Designers, Erattupetta Pala, Kerala, India

    This paper presents the application of damage avoidance de- sign philosophy in a mast, to develop an appropriate mecha- nism to mitigate the effects of an earthquake by using supple- mental cable damping system with fuse-bars parallel to the dampers. The control system

    consists of supplemental dampers acting through a cable con- nected to the structure on the sides of the steel structure. The cable layout is determined iteratively based on the first mode characteristics to counteract the inertial forces in the structure, in a way to reduce the overturning moments [4]. Rigorous stud- ies are conducted on the structure to develop a supplemental damping mechanism. The concept development and design are carried out using capacity-demand spectrum method and is verified by nonlinear time history analysis using SAP 2000, to study the structural response of steel structure with and without supplemental cable damping systems and structural fuse-bars.

  2. MODELLING & ANALYSIS OF STEEL MAST

    1. Mast Structure

      The mast structure used in this study is shown in Fig.1. The mast is with a height of 50 m; with vertical members (2 ISA 130x130x10), cross braces (ISA 70x70x8) and mast body (ISA 90x90x6) of density 7849 kg/m3, Youngs modulus, E 199947.48 N/mm2 and Poissons ratio 0.3.The first 3 mode shapes and their respective time periods are given in Fig.2. A response spectrum analysis was performed on the structure. The mast is analyzed for El Centro spectrum. It is observed that in the direction of U1 degree of freedom, the maximum dis- placement is 0.147004m.

    2. Mast with cable

      An electric mast is modeled with cables [1], [2] of diame- ter 0.0287m in SAP 2000 as shown in Fig.3.The first 3 mode shapes of the mast structure with cables are 0.46849 sec, 0.37402 sec and 0.26482 sec respectively. A response spectrum analysis was performed on the structure. The mast is analyzed for the El Centro spectrum. It is observed that in the direction of U1 degree of freedom, the maximum displacement is 0.019785m.

      Fig.2. First 3 mode shapes of the steel mast of time periods 0.77867 sec, 0.68373 sec and 0.40106 sec respectively.

      Fig.1. 3D Model of the Steel Mast

    3. Discussion of Proposed Configuration

      An approximate supplemental cable damping system is cho- sen by taking into account the dominant mode shape of Steel struc- ture, and is fixed on either side of the structure. The structure is analyzed for El Centro (1940) ground excitation. The procedure is continued by varying the supplemental damping parameters and cable profiles and number of supplemental cable damping system till there is a significant reduction in the seismic response of the structure. The obtained near optimum cable layout and supple- mental cable dampers parameter from iterative method is given as: Damper Stiffness K-1926.39 KN/m

      Damping Coefficient C-3.71 KN-S/m Damping exponent -0.2

      Cable diameter-28.6608mm

    4. Implementation of structural fuse system

      The required fuse behaviour is obtained by defining the hinge property in the fuse element hence above a threshold magnitude of earthquake; the fuse will yield first and keeps the structure, sup- plemental damping system elastic [5],[6],[7]. Thus fuse properties can be chosen, based on the performance objectives, and hinge properties can be set. Table 1 shows the reduction in floor displacement due to the deployment of structural fuse system.

      Fig.3. 3D Model of the Steel Mast with cables

    5. Nonlinear Seismic Response (Pushover analysis) of the Steel mast

      A nonlinear pushover analysis is performed on steel structure with and without supplemental cable dampers and structural fuse- bars. Fig.4 shows the capacity demand curves of steel structure. Fig.5 shows the state of the structure at performance point.

      Fig.6 shows the capacity demand curves of steel mast with sup- plemental dampers and fuse-bars. Fig.7 shows the state of the mast with supplemental dampers and fuse-bars at performance point.

      Fig.4. Capacity demand curves of steel mast

      Fig.5. State of Steel Mast at performance point

      Fig.7. State of Steel Mast with supplemental dampers and fuse-bars at per- formance point

    6. Evaluation of Seismic Performance of the Mast

      It is observed from the pushover analysis of Steel mast that at performance point time period ( Teff ) is 0.571 sec and the corresponding deformation step falls in between step 8 and 9. Per- formance of the structure is within operational level. In case of structure with supplemental cable damping system, the capacity against demand showed a significant improvement. The perfor- mance point time period (Teff) observed to be 0.657 sec .The cor- responding deformation step shows that structure behaves elas- tically without any hinge formation at performance point. The displaement at the performance point reduced from 0.003471m to 0.001546m, when supplemental cable damping system with fuse bars parallel to the damper is applied on the steel structure. Thus it can be concluded that the supplemental damping systems with fuse bars parallel to the damper have improved the global behaviour of the structure.

      Fig.6. Capacity demand curves of steel mast with supplemental dampers and fuse-bars

  3. SUMMARY

    Seismic performance is measured by the state of damage un- der a certain level of seismic hazard. Non-linear time history anal- ysis of the steel mast shows that with the deployment of supple- mental damping system with structural fuse bars in parallel to these dampers in the structure, the maximum lateral displacements got reduced from 0.126781m to 0.031286m. Its seen from the study that Structural fuse bars in parallel to the supplemental cable damping system can reduce maximum lateral displacement in the steel mast to 0.25 times of that of steel mast without supplemental damping system and structural fuse bars. Cable layout is deter- mined iteratively based on the first mode characteristics is fairly sufficient in counteracting the inertial forces.It is observed from nonlinear pushover analysis that, supplemental damping system has improved the capacity of the steel structure.Thus it can be con- cluded that the supplemental damping systems can improve the global behaviour of the structure.Hence a with fuse-bars can re- duce the to damage during a seismic event.

  4. CONCLUSION

Analysis and design of masts against earthquake effect is very important by using DAD Philosophy. Recent and promising ad- vances in the field of Seismic Engineering are Damage Avoidance Design (DAD) philosophy to improve the seismic performance for mast like structures. Steel Mast using a supplemental cable damping system with structural fuse provides a cost-effective way of controlling structural deformation and damage under earthquake excitations. The structural fuse can be readily replaced after a ma- jor earthquake without interfering with the primary structural sys- tem. The structural displacement reduces 0.25 times of that of mast without the supplemental damping system and fuse-bar when excited for El Centro spectrum. Supplemental damping systems with structural fuse are simple, and exhibit reliable characteristics which can be adopted to enhance the seismic performance of the structure.The study shows that the performance of supplemental

cable damping system and structural fuse bars are satisfactory in improving the response of the structures.

APPENDIX A: NUMERICAL EXAMPLE FOR DESIGN OF SUPPLE- MENTAL CABLE DAMPING SYSTEM

    1. The target design drift max is chosen as 1% for a 500

      year event.

    2. Target displacement, Xmax=max. Heff=0.01x =0.7×50 = 0.35m

    3. Iteration

      1. Assume total effective damping tot eff =26.4 %

      2. Spectral amplification factor Bl =

        = =1.647366

      3. Structural demand Cd = =0.065351

      4. Capacity of bare structure = =0.041

      5. Capacity of supplemental System required = Cd –

        =0.024351

        c max d

      6. Supplemental damping required is equal to =0.93 C sup (X )0.04 (C )-0.84=21.47%

      7. Total effective damping = tot eff = str eff + fr hy +

        =5% + 0% +21.47% = 26.47%

    4. For the cable damper with structural fuse configuration, the supplemental capacity is divided between the damp- ers and fuses as

= +

Therefore =Capacity provided by the dampers= 13.235% and = Ca- pacity provided by the fuse=13.235%.

REFERENCES

  1. Gokhan Pekcan, John B.Mander, Stuart S.Chen2000: Balancing Lateral Loads using Tendon-Based Supplemental Damping system.- Journal of Structural Engineering ASCE.

  2. Jack J.Ajrab, Gokhan Pekcan, and John B. Mander-2004:Rocking Wall- Frame Structure with supplemental Tendon System-Journal of Structural Engineering ASCE.

  3. Mander, J. B., and Cheng, C-T. 1997. Seismic Resistance of Bridge Piers Based on Damaged Avoidance Design, Technical Report NCEER- 97-0014, NCEER, Department of Civil and Environmental Engineering, State University of New York at Buffalo,.

  4. Manoj C.M, 2014,Performance of Supplemental Cable Damping system in Mitigating Torsional Response, Mtech Thesis, Department of Civil Engineering, Saintgits College of Engineering, Kottayam, 2014

  5. Ramiro Vargas and Michel Bruneau, 2007: Investigation of the Structur- al Fuse Concept, Earthquake Engineering Research Award Number EEC- 9701471, University at Buffalo.

  6. Ramiro Vargas and Michel Bruneau,: 2009 Analytical Response and Design of Buildings with Metallic Structural Fuses. I, Journal of struc- tural engineering ASCE

  7. Ramiro Vargas and Michel Bruneau/ April 2009.Experimental response of Buildings designed with Metallic Structural Fuses. II, Journal of structural engineering ASCE

  8. SAP 2000 Web Tutorial 1, issued: 1998, Computer and structures, Berke- ley, California, USA.

  9. Computers & Structures, Inc. (2003), SAP 2000 Analysis Reference Man- ual, Berkeley, California: CSI.

  10. FEMA 273, 1997 NEHRP Guidelines for the Seismic Rehabilitation of Buildings, Building Seismic Safety Council for the Federal Emergency Management Agency (Report No. FEMA 273), Washington, D.C.

  11. FEMA 274, 1997 NEHRP Commentary on the Guidelines for the Seismic Rehabilitation of Buildings, Building Seismic Safety Council for the Fed- eral Emergency Management Agency (Report No. FEMA 274), Washing- ton, D.C.