Mechanism of Heat and Mass Transfer in Sandwiched Fibrous Insulations Subjected to Moisture Absorption and Condensation

DOI : 10.17577/IJERTV2IS111103

Download Full-Text PDF Cite this Publication

Text Only Version

Mechanism of Heat and Mass Transfer in Sandwiched Fibrous Insulations Subjected to Moisture Absorption and Condensation

Amit Kr. Singh Chauhan1, Ajitanshu Mishra2, Ujjwala Pandey3, S.J. Pawar4

Research Scholar1,3, MNNIT Allahabad, Assistant Professor 2, Invertis University Bareilly,

Associate Professor4, MNNIT Allahabad

Abstract

This paper presents experimental and theoretical modeling investigation of heat and moisture transfer within Glass fibre reinforced polymer composite (GFRP) Laminates subjected to variable environmental conditions. Under various circumstances, moisture can appear in the insulation matrix. Since the temperature at the boundary changes dynamically with meteorological conditions, heat and mass transfer and moisture between boundaries can appear in this case. A transient model of the heat and mass transfer, including the sorption and condensation processes was studied. The paper includes a numerical model considering the dynamical changing of the boundary temperatures. A parametric study considering different amplitudes of temperature change, different moisture masses and different thicknesses of the insulation matrix was made. The accumulation and distribution of water content is a combined result of moisture absorption, condensation and liquid water movement. It was found that a relatively small mass of water in the insulation matrix can result in a significantly increased average heat flux during a periodic cycle. The numerical results were compared with experiments and found in good agreement with the numeric.

  1. Introduction

    Heat and moisture transfer in porous media with phase change is important to a wide range of scientific and engineering fields [1,2] such as civil engineering, energy storage and conservation, as well as functional clothing design [3], etc. Because of presence of some cracks and flaws in these facings (fabrics), the untight junctions between them and the inappropriate storage, moisture can appear in insulation matrix. Furthermore, because

    of the fabrics high tightness, the drying is usually not possible. The presence of this moisture can result in a physical and chemical deterioration of the insulation matrix and thin coverings, which reduces the life time of the insulation system. In addition, the insulating properties of whole system tend to deteriorate.

    Jintu fan et al. [5] considered a model of coupled heat and moisture transfer with phase change and mobile condensates in fibrous insulation and concluded that the moisture movement within the batting was induced by the pressure gradient. Kyunghoon Min et al. [6] used a mathematical model to simulate the heat and moisture transfer from skin to environment through fabrics by including the radiation heat transfer between surfaces and the surface diffusion along fibers. The result shows that the contributions of radiation and conduction through air are approximately 20% each of the total heat flux. Huijun Wu, Jintu Fan [7] evaluated the effect of positions of different types of battings on the moisture accumulation and thermal insulation performance of the clothing assemblies. They found that placing the hygroscopic wool batting in the inner region (i.e. closer to the body) and the non-hygroscopic polyester batting in the outer region (i.e. away from the body) could reduce the moisture accumulation within and the total heat loss through clothing assemblies. S. Veiseh et al. [8] determined the conductivity of three kinds of mineral wools (glass wool, rock wool, and slag wool) by using reference curve concept. This concept was also used to evaluate the thickness and mean temperature's effects on fibrous insulation matrix by using different models. R. Arambakam et al. [9] found that heat conduction through the solid fibrous structure increases by increasing the materials

    solid volume fraction, fiber diameter, and fibers through-plane orientations. The in-plane orientation of the fibers, on the other hand, did not show any significant influence on the materials conductivity. It was also shown that the microstructural parameters of fibrous insulations have negligible influence on the materials performance if the conductivity of the solid phase is close to that of the interstitial fluid.

    Developing their own model, Motakef and El- Masri [10] and Shapiro and Motakef [11] studied condensate accumulation and its movement inside the thermal insulation. A major discrepancy in the temperature profile for their modeling and measurements occurred in the condensation zone. Wijeysundera et al. [12] later upgraded the study by developing a non-stationary numerical model for a determination of the condensate accumulation in the specimen. The model corresponds well with the measured data for the first 70 h of the coupled heat and mass transfer process. Thomas et al. [13] monitored the temperature change and moisture migration in an initially wet glassfiber insulation slab with impermeable boundaries subjected to one-dimensional temperature gradients on a guarded hot plate.

    In previous researches we found that in most of the cases, while considering a local moisture source, after a number of periodic cycles the moisture spreads approximately equal all over the fibrous insulation matrix. Because of that we can assume, the mass transfer can be studied one dimensionally.

  2. Problem Formulation

    The model was developed by considering one- dimensional with coupled heat and mass transfer in fibrous thermal insulation with impermeable boundaries. And hence for an arbitrary changing of boundary temperatures, the calculation for heat and moisture transfer as well as the fields related to temperature and moisture concentration can be done easily. In the present work, the coupled heat and moisture transfer through fibrous insulations of GFRP was also investigated by an experiment using some tests. For developing the model the following assumptions were taken into account.

    1. The insulation matrix is homogenous.

    2. A local thermal equilibrium exists between the solid, liquid and gas phases.

    3. Convection is negligible in the insulation matrix.

    4. The liquid phase is immobile.

    5. The total gas-phase pressure in the insulation matrix is constant.

    6. A local thermal equilibrium exists between the solid, liquid and gas phases and a local moisture equilibrium exists between the sorbed moisture at the surface of fibers and the moisture content of the

      air and between liquid water and the moisture content of the air.

      The following equations are used for modeling of Heat and mass transfer and solved by using Crank- Nicholson implicit method.

      Since radiation will not affect much at low temperature and as per assumption no. 3 hence energy equation can be written as:

      Energy equation:

      .{1}

      Water-Vapor diffusion equation:

      .{2}

      Where is the rate of sorption/desorption, condensation/evaporation (kg/m3s) can be determined by summing the terms as rate of moisture uptake and release during sorption/desorption and the evaporation/condensation process. And hence can be written as:

      .{3}

      Where

      .{4}

      is the rate of sorption/desorption which can be related to mass of sorbed moisture (u).

      Figure 1. Schematic diagram of insulation matrix.

      And

      .{5}

      is the rate of conservation of liquid phase.

      Local values of the thermal conductivity of the insulation matrix change significantly with the liquid content and can be determined using following equation

      .{6}

      For th same case the specific heat capacity can be determined as:

      .{7}

      and the density

      .{8}

      The diffusion coefficient of the water vapor in the insulation matrix is assumed to be a function of the temperature, the turtousity of the insulation matrix and the volume fraction of the gaseous phase. It can be determined by:

      .{9}

      Since total volume is always constant. Hence expression for different volume fractions refers to:

      ….{10}

      The rate of heat generation (q.) in equation {1} can be determined by summing of the heat source/sinks, appearing during sorption/desorption and condensation/evaporation process.

      .{11}

      The relative humidity () can be expressed as: =C/Cs .{12}

      The term Cs can be determined by using saturation- pressure equation[24] and by considering the ideal gas law into consideration.

      .{13}

      The binary diffusion coefficient of water vapor used in equation (6) can be determined by using the following relation[24].

      .{14}

      2.1 Boundary conditions

      The temperatures at the boundaries changes with meteorological parameters and with the temperature of the indoor environment and hence can be expressed as:

      .{15}

      .{16}

      For Moisture transfer, since insulation matrix boundaries are impermeable to moisture. Hence

      .{17}

      Firstly we begins with a determination of the first iteration of the temperature field (Eq. (1)).

      The sorption/desorption (so) and condensation/evaporation (fg) rates are determined next by iterating the vapor diffusion equation (Eq. (2)). The process was repeated untill upto the convergence criteria is reached, after then the next variation of the temperature field (Eq. (1)) is determined, using updated values of so, fg. The

      temperature-dependent parameters (D12 Eq. (14), Cs Eq. (13)) and the liquid-content-dependent

      parameters (De Eq. (9), ke Eq. (6), cp,e Eq.

      (7), and density Eq. (8)) were updated during every iteration. The iteration procedure continues until the residuum of the temperature and the concentration fields are less than 10-4 and 10-7, respectively. After that the next time step calculation starts.

  3. Experiment:

    Following tests were included in experiment.

    3.1 Measurement of moisture absorption

    For measuring moisture absorption, condensation and other properties, the following steps were used while performing the experiment:

    [1]. A number of samples of GFRP laminated glass were taken of some specific dimensions.

    [2]. The top and bottom layer of the specimen were condition at an air conditioned room with temperature at 25.0 ± 0.50C and humidity at 65 ± 5% for at least 24 h.

    [3]. Weigh and record the weights of each sample.

    [4]. All Samples were exposed to temperature controlled water containers.

    [5]. The samples were kept in water for different time durations such as 3 days, 6 days, up to 18 days etc.

    [6]. After a pre-set time (i.e., 3, 6, 9, 12, 15 or 18 days), take out each sample and weigh them immediately using an electronic balance.

    [7]. Calculate the percentage of moisture or water accumulation due to absorption or condensation on each sample by

    2.2 Solution procedure

    .{18}

    ….{19}

    Equation {1} and {2} were discretized using Crank-Nicholsan Method for numerical calculation. Numerical code was written in the numerical simulation environment Matlab. The tri-diagonal system of equations obtained by the discretization was solved using the TDMA algorithm [25].

    where, Wai is the weight of the ith sample after test for a pre-set period of time, Woi is the weight of the ith sample before testing, and Wci is the increase in water content in percentage.

    Table 1 : specimens exposed to water

    Sample no.

    Weight of sample with exposure time (in grams)

    0 days

    3 days

    6 days

    9 days

    12 days

    15 days

    18 days

    1.

    17.7

    18.4

    19.2

    19.6

    19.8

    19.9

    20.2

    2.

    18.9

    20.5

    21.6

    22.1

    22.4

    22.6

    22.8

    3.

    19.0

    19.8

    20.8

    21.9

    22.2

    22.4

    22.6

    4.

    19.4

    20.2

    20.8

    21.3

    21.9

    22.2

    22.4

    5.

    19.6

    20.6

    21.2

    21.6

    22.0

    22.4

    22.5

    Total weight

    93.6

    99.5

    103.6

    106.5

    108.3

    109.5

    110.5

    % of weight gain

    0

    6.3034

    10.6837

    13.782

    15.7051

    16.9871

    18.0555

    Rate of absorption

    0

    1.9666

    0.6833

    0.3222

    0.15

    0.08

    0.0555

    Change in tensile modulus

    0.97

    0.964

    0.952

    0.945

    0.924

    0.913

    0.902

    3.2 Mechanical Characterization test: Laminated glass interlayer plays a mechanical rule, both at rupture and in the serviceability domain, it is important to evaluate the consequences of weathering on the mechanical properties of interlayer polymer. For investigating the damage of poly (vinyl butyral) laminated glass under weathering action, specimens were subjected to laboratory degradation by moisture, UV radiation and thermic cycles.

    3.2.1 Accelerated Moisture Action

    Specimens consisting of two composite glass laminated with PVB interlayer with thickness 8- 1.52-8 mm and thickness 8-0.76-8 mm respectively with diameter 23.06 mm were taken. Some of them were intended for environmental damage. Particularly, some specimens were subjected to moisture action keeping them suspended over a covered thermostatic bath at the temperature of 50° (about 100% R.H.). Accelerated moisture damage can hardly be compared to some environmental conditions; at the moment our aim is to measure the consequences of extreme moisture action rather than try to reproduce a specific field situation.

    As a consequence of moisture diffusion, laminated glass began to exhibit opacity from the boundary towards the center of the button. After 33 days (about 809 hours) specimens were opaque for some millimeters; specimen with 8-1.52-8 mm was conditioned at room temperature and humidity, till it recovered the original transparency, and then tested. Other 12 specimens, six of them 8-0.76-8 mm and six of them 8-1.52-8 mm, were subjected to moisture action with the same procedure for about 226 days (5425 hours). At the end they were completely opaque, so that the complete transparency recovery took about six months. Three of the six specimens 8-0.76-8 mm were also affected by delamination, from the boundary towards the center.

  4. Results & Discussions

    The aim of this work is to investigate the absorption of moisture in different glass composites under different moist environmental conditions to understand the overall effect of moisture absorption on the weight and mechanical property. The experimental results are presented in table 1.

      1. Effect of moisture absorption on weight and tensile property

        The way of moisture absorbed is dependent upon many factors like type of climatic exposue, severity of exposure, humidity and temperature. The analysis of results is done by plotting the curve of weight gain verses exposure time and tensile modulus verses exposer time as shown in graph 1 and 2. Hence investigation of the effect of moisture impact on GFRP composite laminates under different moisture environmental conditions were done. It can be easily observed that while in start, there is almost a linear increase in the equilibrium moisture content, then after gradually increases and expected to approaches constant saturation level. In the graph 2, it was observed that tensile modulus decreased to some extent with the presence of moisture. Fibre strength was also negatively affected, possibly due to either leaching out of the glass fibres interface layer or glass fibre embrittlement, less effective bonding and load distribution at the fibrematrix interface.

      2. Effect of water on tensile modulus

    The tensile strength of GFRP laminates exposed to water at room temperature is decreases gradually over exposure period of 18 days after continuous exposure the reduction of tensile modulus expected to maintain constant. The reasons can be initially rapid entering of water particles into fibre- matrix interface due to capillary action. After certain period of time, a saturation stage is reached and no more water seep into fibre matrix phase. All the voids of laminates filled with moisture and which act as a plasticizer to fevor the property.

  5. Conclusions

    The experimental results shows weight gain and reduction in tensile modulus of GFRP Specimens in water. The GFRP Composites were experimental investigated and found the remarkable reduction in weight as the effect of moisture absorption. The mechanical strength (tensile modulus) of GFRP Composites were also found in effective decreased values which are exposed to water and at room temperature for different exposure time.

    Due to presence of moisture in matrix of composite material causes following factors:

    1. Swelling of matrix,

    2. Debonding of inter-phase,

    3. physical damage of matrix inter-phase and

    4. hydrolysis of composite materials

    these all factors are also the main reasons for the reduction in tensile strength.

    The following conclusions may be drawn for this study:

    1. The Composite material moisture absorption is more.

    2. The presence of moisture or water particles in the matrix, fiber-matrix interface of composite materials attack on the glass fibres, all these are the reason for the reduction of mechanical properties. But in both normal and frozen conditions the damage is more severe in case of frozen moisture.

  6. References

[1]. D.A. De Vries, The theory of heat and moisture transfer in porous media revisited, Int. J. Heat Mass Transfer 30 (7) (1987) 13431350.

[2]. A. Bouddour, J.L. Auriault, M. Mhamdi- Alaoui, Heat and mass transfer in wet porous media in presence of evaporation condensation, Int. J. Heat Mass Transfer 41 (15) (1998) 22632277.

[3]. J.L. Spencer-Smith, The physical basis of clothing comfort, part 6: application of the principles of the design of clothing for special conditions, Cloth. Res. J. (1978).

[4]. W.C. Thomas, G.P. Bal, R.J. Onega, Heat and Moisture Transfer in a Glass Roof-insulating Material, ASTM STP 789, 1983, pp. 582601.

[5]. Jintu Fan, Xiaoyin Cheng, Xinhuo Wen, Weiwei Sun, An improved model of heat and moisture transfer with phase change and mobile condensates in fibrous insulation and comparison with experimental results, International Journal of Heat and Mass Transfer, 47 (2004) 23432352.

[6]. Kyunghoon Min, Yangsoo Son, Chongyoup Kim, Yejin Lee, Kyunghi Hong, Heat and moisture transfer from skin to environment through fabrics: A mathematical model , International Journal of Heat and Mass Transfer, 50 (2007) 52925304.

[7]. Huijun Wu, Jintu Fan, Study of heat and moisture transfer within multi-layer clothing assemblies consisting of different types of battings , International Journal of Thermal Sciences, 47 (2008) 641647.

[8]. S. Veiseh, N. Khodabandeh and A. Hakkaki- Fard, Mathematical models for thermal conductivity density relationship in fibrous thermal insulations for practical applications, Asian Journal of Civil Engineering (Building and Housing), Vol. 10, No. 2 (2009) Pages

201-214.

[9]. R. Arambakam, H. Vahedi Tafreshi, and B. Pourdeyhimi, A simple simulation method for

designing fibrous insulation materials, Materials & Design, Vol. 44, Pages 99-106, 2013.

[10].S. Motakef, M.A. El-Masri, Simultaneous heat and mass transfer with phase change in a porous slab, Int. J. Heat Mass Transfer 29 (1986) 15031512.

[11]. A.P. Shapiro, S. Motakef, Unsteady heat and mass transfer with phase change in porous slab: analytical solutions and experimental results, Int. J. Heat Mass Transfer 33 (1990) 163173.

[12].N.E. Wijeysundera, B.F. Zheng, M. Iqbal, E.G. Hauptmann, Numerical simulation of the transient moisture transfer through porous insulation, Int. J. Heat Mass Transfer 39 (1996) 9951004.

[13].W.C. Thomas, G.P. Bal, R.J. Onega, Heat and Moisture Transfer in a Glass Roof-insulating Material, ASTM STP 789, 1983, pp. 582601.

[14].S. Motakef, M.A. El-Masri, Simultaneous heat and mass transfer with phase change in a porous slab, Int. J. Heat Mass Transfer 29 (1986) 15031512.

[15].A.P. Shapiro, S. Motakef, Unsteady heat and mass transfer with phase change in porous slab: analytical solutions and experimental results, Int. J. Heat Mass Transfer 33 (1990) 163173.

[16].N.E. Wijeysundera, B.F. Zheng, M. Iqbal, E.G. Hauptmann, Numerical simulation of the transient moisture transfer through porous insulation, Int. J. Heat Mass Transfer 39 (1996) 9951004.

[17].Laura Andreozzi, Silvia Briccoli Bati, Mario Fagone, Giovanna Ranocchiai, Fabio Zulli, Analysis of environmental damage consequences on viscous thermo elastic properties of a polymer interlayer.

[18].P. Sampath Rao, Dr. M. Manzoor Hussain, R.Kishore, Moisture Absorption Evolution of Gfrp Laminates Subjected To Different Environmental Conditions, IOSR Journal of Mechanical and Civil Engineering, Volume 2, Issue 5, 2012, PP 33-38.

[19].Jintu Fan, Xiaoyin Cheng, Yi-Song Chen, An experimental investigation of moisture absorption and condensation in fibrous insulations under low temperature, Experimental Thermal and Fluid Science, 27 (2003) 723729.

[20].Uro Leskovek a, Sao Medved, Heat and moisture transfer in fibrous thermal insulation with tight boundaries and a dynamical boundary temperature, International Journal of Heat and Mass Transfer, 54 (2011) 4333

4340.

Leave a Reply