Geotechnical Investigation of a Collapsed Building Site in Port Harcourt, Rivers State Nigeria

DOI : 10.17577/IJERTV8IS040082

Download Full-Text PDF Cite this Publication

Text Only Version

Geotechnical Investigation of a Collapsed Building Site in Port Harcourt, Rivers State Nigeria

1Youdeowei, P.O

1Institute of Geosciences and Space Technology (IGST), Rivers State University, Port Harcourt,

Rivers State, Nigeria.

2Rowland-Lato, E.O.

2Works and Services Department, University of Port Harcourt, Choba, Rivers State, Nigeria.

Abstract:- The recent collapse of a 7-storey building still under construction in Port Harcourt which caused the loss of several lives led the State government to set up a judicial panel of enquiry to find out the immediate and remote causes. A geotechnical team was commissioned to investigate the sub- soil conditions at the site. This study and its findings are informed by these activities. The sub-soil investigation was conducted by drilling five (5) well spaced and site representative boreholes with a light cable Percussion rig to depths of 35m each. Soil samples were logged and SPT soundings were conducted. Undisturbed and disturbed soil samples were also recovered for Laboratory analysis in accordance with BS 1377. The soil stratigraphy revealed brownish silty clay overburden of 6m depth with moderate plasticity underlain by medium grained, loose to moderately dense sand (N values of 3-33) to the maximum drilled depth. Natural moisture content of the Clay soils ranged from 16.20 to 21.30% while the plasticity index varied from 15.66 to 21.33%. The shear strength parameters of these c- soils gave average values of 46kPa and 4.5 degrees as undrained cohesion and undrained angle of internal friction, respectively. The net foundation pressure or allowable bearing capacity for a shallow foundation at the site was computed as 135KPa at a settlement of 33mm for a foundation breadth of 1 to 2.5m to a depth of 3m. For the deep foundation, the safe pile load or allowable pile (axial) capacity at a depth of 35m were calculated for the five (5) boreholes. The result gave average values of 406KN and 508KN for tubular driven steel cased piles of 14 (356mm) diameter and 16 (406mm) diameter, respectively. It was strongly recommended that all piles be terminated at the medium dense sand layer at a depth not less than 30m. Furthermore, the pile foundation design should be validated with a pile load test to confirm the design load adopted and pile settlement. It was noted that inadequate depth of pile embedment and the absence of a pile load test to determine the safe load capacity of the piles must have been major causes of the subsoil and structural foundation failure.

Key words: Collapsed building, geotechnical investigation, bearing capacity, pile foundation, pile load test, Port Harcourt.

INTRODUCTION

The frequency of collapsed buildings in recent years resulting in much loss of lives, properties and superstructures in Port Harcourt has been a great cause for concern. Reasons adduced are mostly ascribed to poor quality building materials. While this may be true, less attention is paid on the sub-surface soil condition that bears

the foundation. The need to understand and determine the load carrying capacity of these soils and recommend the appropriate foundation type for the structures as the basic geotechnical and civil engineering requirement before construction is of utmost importance [1]; [2]. This study sadly is coming only after yet another failed building episode with all its attendant grave consequences.

The collapse of a 7-storey building still under construction on the 23rd of November, 2018, at the GRA phase 2, Port Harcourt which caused the loss of several lives led the State government to set up a judicial panel of enquiry to find out the immediate and remote causes. A geotechnical team was commissioned to investigate the sub-soil conditions at the site. This study and its findings are informed by these activities. The purpose of this study is to present the details of the geotechnical investigation activities at the collapsed building site. The investigation is aimed at providing geotechnical information for the possible causes of the collapsed building.

STUDY LOCATION AND GEOLOGY

The project site is in Port Harcourt, Rivers State, within the Niger Delta region. It lies within a sub-horizontal geomorphologic terrain with a measure of undulations arising from uneven surface area erosion. Ground elevation range between 10-12 meters above mean sea level. The local geology is of the coastal plain sand, which is Miocene in age and form parts of the uppermost strata of the outcropping Benin Formation [3]; [4]. These consist of extensive thickness of brownish, coarse to medium sand with subordinate clay and silt. There are drainage problems with seasonal and temporary flooding due to heavy rainfall (mean annual rainfall exceeds 2000mm.) and rise in groundwater table. The site is about 120m from the nearby Ntawoba creek. The area is associated with luxuriant freshwater vegetation typical of a tropical rainforest.

METHODOLOGY

  1. Field Exploration

    Subsurface conditions at the site were studied by boring Five (5) holes (BH) to depths of 35m each at the collapsed building site using a light cable Percussion

    rig of the Pilcon Wayfarer type with the aid of augers, clay cutter and shell. Percussion drilling method permits more accurate sampling of the cuttings as brought up with the bailer and more accurate determination of groundwater levels. Soil samples were retrieved at depths of 1.0m intervals and at points where a conspicuous change in soil lithology was observed, for visual examination, laboratory testings and classification. Undisturbed cohesive soil samples were recovered with the aid of U-4 tubes and as boring advanced, Standard Penetration Test (SPT) was conducted to determine the penetration resistance values of cohesionless soils at specific depths within the

    boreholes. It is a useful tool to determine in situ density and relative density. The boreholes layout is presented in Fig.1, while the variation of SPT values with depth for a representative borehole at the site is seen in Fig.2. Figure 3 shows the drilling activities by the field crew at the site.

    The water level at the site was generally at about 3.6m below the ground level at the time of investigation in December, 2018. This will be subject to seasonal fluctuations. The site is also about 120m from the Ntawoba creek. The implication is that groundwater recharge may be enhanced with water infiltrating the confining permeable layers from the creek.

    Fig. 1: Layout Of Boreholes At The Site

    Fig. 2: Boreholes Log with SPT Values (BH1)

    Fig. 3: Field crew drilling at the collapsed building site.

  2. Laboratory Tests

    The conventional soil mechanics tests relevant to the intended project were carried out. The following tests were conducted in accordance with BS 1377[5] Method of test for soils for Civil Engineering purposes which is equivalent to ASTM (1979)[6]. The tests were to enable the evaluation of the gradation, consistency, strength and settlement characteristics of the sub-soils at the project site that will influence the choice of foundations and design considerations.

    -Classification Tests

    This was obtained based on the following laboratory test results:

    1. Atterberg Limits Tests (consisting of liquid and plastic limits).

    2. Particle size distribution.

      The cohesive soil samples of BH1 to BH5, which were obtained from the borings, were analyzed by wet sieving to obtain the coarse grained fractions of the soil sample, while the cohesionless soil fractions were subjected to dry sieving. The Atterberg limits of the platic soils were analyzed using the Casagrande liquid limit apparatus.

      Soil classification was based on the British soil classification system (BSCS) and the unified soil classification system (USCS) and is shown in Table 1, while the table and graphs of the particle size distribution is presented in Figure 4. Soils that have the same classification tend to have the same engineering behavior [7].

      STARTRITE MAYTON CO.NIG.LTD PORT HARCOURT

      STARTRITE MAYTON CO.NIG.LTD PORT HARCOURT

      Fig. 4: Particle Size Distribution Curve of Bp at 8m Sample Depth

      -Triaxial Test

      Unconsolidated undrained triaxial compression tests were carried out on cohesive soil samples of BH1 to BH5. The shear strength parameters of undrained cohesion (cu) and undrained angle of internal friction (u) of the c- soils are obtained from unconsolidated undrained triaxial compression tests. Three soil samples were respectively subjected to cell pressures of

      100kN/m2, 200kN/m2 and 300kN/m2 and the soil samples were sheared to failure by incrementally loaded deviator stress. The deviator stresses at failure of each cell pressure were analyzed and the shear strength parameters of the soil evaluated. A plot of the Mohr circle for the respective major principal stresses at failure and the applied cell pressures of a representative cohesive soil sample are shown in Fig.5.

      Fig. 5: Result of Shear Strength Test of Silty Clay Soil in Borehole 2

      -Consolidation Test

      One-dimensional oedometer consolidation tests were carried out on the cohesive soil samples of the boreholes. This test is aimed at determining the relevant settlement properties of the soil which

      are used in evaluating foundation settlement. The values of coefficient of volume compressibility (Mv), initial void ratio (eo), specific gravity (Gs) and natural moisture content (w%) of a representative soil sample is also shown in Fig. 6.

      STARTRITE MAYTON CO.NIG.LTD PORT HARCOURT

      STARTRITE MAYTON CO.NIG.LTD PORT HARCOURT

      Fig. 6: Consolidation Test Result of Silty Clay Soil at 3m Depth in BH3

      DISCUSSION OF RESULTS

      Soil Stratigraphy and Classification

      Classification tests revealed the plastic soils as generally consisting of grey to brownish, CLAY

      of intermediate plasticity and medium grained, medium dense, SAND up to the depth of investigation from the ground surface. A summary of the Atterberg limits and plasticity index of the soils are shown in Table 1.

      Table 1: Atterberg limits.

      Borehole

      No.

      Sample Depth (m)

      Liquid Limit

      (%)

      Plastic

      Limit (%)

      Plasticity Index (%)

      BSCS

      USCS

      1

      0.75 – 6.00

      6.00-35.00

      37.26

      Np

      18.07

      Np

      19.19

      Np

      CIS

      SPu

      CL SP

      2

      0.75 – 6.00

      6.00-35.00

      40.12

      Np

      18.82

      Np

      21.30

      Np

      CIS

      SPu

      CL SP

      3

      0.00 – 6.00

      6.00-35.00

      32.33

      Np

      16.67

      Np

      15.66

      Np

      CLS

      SPu

      CL SP

      4

      0.00 1.50

      1.50 – 3.00

      3.00-35.00

      Np 36.28

      Np

      Np 26.25

      Np

      Np 20.03

      Np

      SPu CIS

      SPu

      SP CL SP

      5

      0.00 – 4.50

      4.50-35.00

      39.78

      Np

      18.45

      Np

      21.33

      Np

      CIS

      SPu

      CL SP

      Shear Strength and Bearing Capacity

      The shear strength parameters were used to calculate the bearing capacity of the soil at foundation depths below the existing ground level. Furthermore, the unit weights of the soils were also determined. The dimensionless bearing capacity factors were used in the bearing capacity analysis for the foundation.

      -Shallow Foundation

      The shear strength parameters cu and u of the cohesive soil samples were obtained from unconsolidated undrained triaxial tests, while shear strength parameter d of the granular soils were evaluated from average SPT-number of the respective stratum. The dimensionless bearing capacity factors after Vesic has been adopted in computing the bearing capacity for shallow foundation:

      qu = cNcSc + D(Nq – 1) Sq + 0.5 BNS

      Where qu = ultimate bearing capacity

      C = undrained cohesion q = effective overburden

      = effective unit weight

      Nc, Nq, Ny = Bearing capacity factors Sc, Sq, Sy = Shape factors

      The net allowable, qn(a), bearing capacity of the soil has been evaluated with a factor of safety (F.S) of 3.0.

      c

      =

      52 kN/m2

      =

      5o

      Nc

      =

      6.49

      Nq

      =

      1.57

      N

      =

      0.45

      =

      21.70-9.81 = 11.89kN/m3

      c

      =

      52 kN/m2

      =

      5o

      Nc

      =

      6.49

      Nq

      =

      1.57

      N

      =

      0.45

      =

      21.70-9.81 = 11.89kN/m3

      Typical calculation of net allowable bearing capacity for BH1 at Df of 1.0m for square footing (B/L=1) is as follows: qu = 1.3cNc + D(Nq – 1) + 0.4 BN

      qn u 1.3x 52×6.49 11.89×1.0x(1.57 1) 0.4 x 11.89 x1x 0.45

      qna FS 3

      =151.67kN/m2

      Similar calculations for BH1 at depths 2.0m, 3.0m and BH 2 to BH 5 at their respective depths were obtained. The submerged unit weight introduced in the analysis is to account for the effect of water on the surcharge component of bearing capacity.

      The calculated bearing capacities could be used in determining the shallow foundation type for the structure. An average bearing capacity of 135kN/m2 is recommended.

      -PILE FOUNDATION

      Axial Pile Capacity Determination

      The type of piles that may be adopted for this project are those that are driven (displacement piles) e.g. pre-cast concrete and steel cased piles. This is so as to enable the monitoring of the piling blow counts and remedy any negative skin friction. However, the versatility and cost effectiveness of a particular type of pile will be the governing factor.

      The safe working load of piles are dependent on factors such as pile diameter, founding depth and method of installation which is usually best determined by a specialist-piling contractor from a pile load test.

      Allowable pile capacities for axial loading for 406mm (16) tubular driven steel pile have been estimated for the project. Soil profile and geotechnical data obtained from the site were used for the analysis. The following relationships were used for the calculations:

      1. Qu = Qb + Qs

      2. Qu = 9CuAb + CuAs for Clay

      3. Qu = Po Nq Ab + ksPo tanAs for Sand Where, Qu = ultimate bearing capacity of pile (kN)

Qb = total end bearing (kN)

Qs = Skin fiction resistance (kN)

Cu = Undrained shear strength of the soil (kN/m2) As = Surface area of pile shaft (m2) = BD

B 2

Ab = Base area of pile shaft (m2) =

4

Po

= effective overburden pressure =

w D

2

B = Diameter of pile

D = Depth of penetration

= Adhesion factor=0.60

= Friction angl between the soil and pile wall = 0.60 ks = Coefficient of horizontal soil stress = 1.5ko

ko = Coefficient of earth pressure at rest = 1-Sin

The calculated ultimate pile capacities for BH1 to BH5 are shown in Table 3 below. Allowable axial pile capacity has been obtaining by applying safety factor of 2.5 for driven piles. Plot of depth of penetration versus allowable pile capacities for 406mm (16) tubular driven steel piles is shown in figure 7.

It is well established that pile foundation design is not complete without pile load tests [8]; it is therefore recommended that a pil load test be conducted at the site to ensure the design adopted can be safely carried.

STARTRITE MAYTON CO.NIG.LTD PORT HARCOURT

STARTRITE MAYTON CO.NIG.LTD PORT HARCOURT

Fig.7: Plot of Borehole Depth Versus Allowable Pile Capacity for 406mm (16) Diameter Driven Casing for Bh4

SETTLEMENT ANALYSIS

Total consolidation settlement (c) has been computed for foundation breadth (B) between 1.00-2.50metres, subjected to a net allowable bearing capacity of 135kN/m2. Based on the soil lithology, the thickness of the consolidating layer for a square foundation is taken as the depth to the point where the induced vertical stress () is equal to 0.55qn [9]. The induced vertical stress () at the centre of the consolidating layer has been used in computing c. The consolidation settlement has been computed from the expression.

pc = gPoed

= mvzH

= mv x 0.55qn x 1.5B

where g = coefficient which depends on the type of clay Poed = settlement as calculated from oedometer tests mv = coefficient of volume compressibility

qn = net foundation pressure B = Breadth of foundation.

An mv value of 0.12m2/MN, which corresponds to the adopted net allowable bearing capacity for the site, has been used in the settlement analysis. The values of total consolidation settlement are presented in Table 2.

Table 2: Settlement Values of Soil.

Foundation breadth, B (m)

Settlement, c (mm)

1.0

1.5

2.0

2.5

13.37

20.05

26.73

33.41

From Table 2, the computed settlement values for a square foundation breadth of 1.00 2.50m is less than the allowable maximum settlements of 65mm suggested by Skempton and MacDonald for isolated foundations and 65- 100mm for rafts on clay [9]. Hence the soil can sustain a bearing pressure not greater than 135kN/m2.

CONCLUSIONS AND RECOMMENDATIONS

The investigation was carried out with the knowledge that a building was constructed at the site and the soils especially at the collapsed area are now overconsolidated (preconsolidated). The implication is that with the vertical effective overburden stresses being once higher at the site, the surcharge loading of the structure has increased the soil cohesion.

The objective of the subsoil investigation was to determine the subsoil conditions prevalent at the location and thereby ascertain the possible causes of the building collapse.

-Soil Classification and Stratigraphy

The information from deep soil borings and laboratory tests were used in determining the soil stratigraphy of the project site.

The different boreholes drilled have a near consistent uniform soil strata, which exist in two major layers. The soil profile generally consists of a 6m thick greyish brown to brown silty clay of intermediate plasticity which is underlain by medium grained, medium dense sand up to the investigated depth of 35m.

-Safe Bearing Capacity

  1. A bearing capacity value of 135kN/m2 adopted for shallow foundation is limited to the overburden soft silty clay which extended to a depth of 3.0m within which the foundation may be situated.

  2. Where the foundation footings are too close to each other, the option of a raft foundation may be considered.

  3. Where the calculated safe bearing pressures are not adequate for the installation of a shallow foundation,

    deep foundation in form of piles are strongly recommended for the structure.

  4. In this country, small diameter piles (up to 450mm/18) are driven piles while large diameter (600mm/24) and above are usually bored piles[8] .

  5. Axial load carrying capacity for 356mm (14) and 406 (16) diameter tubular driven steel cased piles were calculated and plots of depth of penetration versus allowable pile capacities for each of the 5 boreholes are presented. It is strongly recommended that all the piles be terminated at the medium dense sand layer at a depth not less than 30m.

  6. The pile foundation design should be validated with a pile load test to provide qualitative confirmation of the design load adopted and pile settlement.

  7. It was noted that inadequate depth of pile embedment and the absence of a pile load test to determine the safe load capacity of the piles must have been major causes of the sub soil and structural foundation failure.

  8. Lastly, it is strongly recommended that the design and construction of the foundation of a future superstructure at the site should be carried out in accordance with good engineering practice as embodied in recognized codes of practice such as the British Standard Institutions BS 6031: 1981, Code of Practice for Earthworks and BS 8004: 1986, Code of Practice for Foundations.

    ACKNOWLEDGMENT

    The authors express their gratitude to the Judicial Commission of enquiry set up by the Rivers State government for the invitation to carry out this independent study.

    REFERENCES

    1. P.O. Youdeowei, Report on sub-soil investigations for foundation of blocks of residential buildings, G.R.A. phase 3, Port Harcourt, unpublished. Submitted to Bimkol Engineering (Nig.) Ltd. Port Harcourt, 1995.

    2. P. O. Youdeowei and H. O. Nwankwoala, Suitability of soils as bearing media at a freshwater swamp terrain in the Niger Delta. Journal of Geology and Mining Research, Vol. 5(3), 58-64, 2013.

    3. R.A .Reyment, Aspects of geology of Nigeria. University of Ibadan Press, Nigeria, p.133, 1965.

    4. K.C. Short and A.J. Stauble, Outline of the geology of the Niger Delta. Bull. Am. Ass. Petrol Geol. 54:761 779, 1967.

    5. B.S. 1377, Methods of test for soils for civil engineering Purpose, British Standards Institution (BS1), London, 1975.

    6. ASTM, Annual book of America society for testing and materials standards, 1289, Philadelphia, 1979.

    7. R.B. Peck, W.E. Hanson, and T.H. Thornburn, Foundation engineering, 2nd Ed. John Wiley, New York, p. 514, 1974.

    8. V.O. Oyenuga, Design and construction of foundations (A practical approach). Asros Ltd, Lagos, p. 214, 2004.

    9. M.J. Tomlinson, Foundation design and construction. Pitman Advanced Publishing Program, London, 6th Edition, p.536, 1995.

Leave a Reply